Connectrix MDS : 97xx Chassis information missing with error message %PLATFORM-2-PS_UNSUPPORTED

Summary: Connectrix MDS : 97xx Chassis information missing with error message %PLATFORM-2-PS_UNSUPPORTED

This article applies to This article does not apply to This article is not tied to any specific product. Not all product versions are identified in this article.

Symptoms

Connectrix MDS Switch doesn't display the chassis information and no module information available.

Hardware
  cisco Unknown MDS Chassis ("Supervisor Module-4")
  Intel(R) Xeon(R) CPU D-1548  with 14270340 kB of memory.
  Processor Board ID JAE24021JBB

  Device name: G3PPSW1063-1I
  bootflash:    3932160 kB
  slot0:              0 kB (expansion flash)

Kernel uptime is 218 day(s), 7 hour(s), 53 minute(s), 30 second(s)



The `show logging logfile` output will continuously the following error message.


`show logging logfile`
2021 Mar 18 08:26:13 G3PPSW1063-1I %PLATFORM-2-PS_UNSUPPORTED: Detected an unsupported power supply 4 DS-CAC97-3KW for CISCO Multilayer Switch(Serial number XXXXXXXXXXX)
2021 Mar 18 08:26:13 G3PPSW1063-1I %PLATFORM-2-PS_UNSUPPORTED: Detected an unsupported power supply 5 DS-CAC97-3KW for CISCO Multilayer Switch(Serial number XXXXXXXXXXX)
2021 Mar 18 08:26:13 G3PPSW1063-1I %PLATFORM-2-PS_UNSUPPORTED: Detected an unsupported power supply 7 DS-CAC97-3KW for CISCO Multilayer Switch(Serial number XXXXXXXXXXX)
2021 Mar 18 08:27:53 G3PPSW1063-1I %PLATFORM-2-PS_UNSUPPORTED: Detected an unsupported power supply 1 DS-CAC97-3KW for CISCO Multilayer Switch(Serial number XXXXXXXXXXX)
2021 Mar 18 08:27:53 G3PPSW1063-1I %PLATFORM-2-PS_UNSUPPORTED: Detected an unsupported power supply 2 DS-CAC97-3KW for CISCO Multilayer Switch(Serial number XXXXXXXXXXX)
2021 Mar 18 08:27:53 G3PPSW1063-1I %PLATFORM-2-PS_UNSUPPORTED: Detected an unsupported power supply 3 DS-CAC97-3KW for CISCO Multilayer Switch(Serial number XXXXXXXXXXX)
2021 Mar 18 08:27:53 G3PPSW1063-1I %PLATFORM-2-PS_UNSUPPORTED: Detected an unsupported power supply 4 DS-CAC97-3KW for CISCO Multilayer Switch(Serial number XXXXXXXXXXX)


Also show module command shows no chassis information could be retrieved and show environment power command shows pdb_get_chassis failure message.

`show module`
Chassis information could not be retrieved`show environment`
pfm_update_chassis_info: pdb_get_chassis failed
show_env_power_dc3_generic:8740 unable to get pdb chassis


Condition:
On 97xx series director class switches with SUP 4 (DS-X97-SF4-K9) module

Cause

.

Resolution

Only workaround available at this time for writing this KB and no fix available.

Workaround:

==========
Switches running NX-OS 8.4(1) - NX-OS 8.4(2a):

Check the capability of standby module and then perform a system switch over if Chassis information are available on standby module.

Note: This command should be run from the standby supervisor (not from the active supervisor) after connecting to it using the Console port of standby supervisor. Console port access needs a access via CE or onsite resource from the Data centre.

From the standby SUP Please check Capability as below:

switch(standby)# show system internal capability | begin CHASSIS
2) Service:platform, Capability:CAP_TYPE_CHASSIS
Description:Sets chasis database
chassis type MDS9700 10-slot chassis
num of slots 10
num of supervisor slots 2
sup slot 0 4
sup slot 1 5
num of fabric slots 6
chassis family 1

To switchover to standby use the following command on active supervisor:

switch# system switchover

Once the switchover is complete and the new standby is up and ready, check the above capability command on both Primary and Standby Supervisor and make sure Chassis information are available.

Note: If the "show system internal capability | begin CHASSIS" return nothing after connecting to the console port of standby supervisor, then to recover, a switch reload is required.


Switches running NX-OS 8.4(2b) onwards:
=================================


Use the following CLI command to add the chassis information.

switch# pfm pdb chassis-info add

Perform the following command and verify chassis information are added.

switch# show system internal capability | begin CHASSIS
2) Service:platform, Capability:CAP_TYPE_CHASSIS
Description:Sets chasis database
chassis type MDS9700 10-slot chassis
num of slots 10
num of supervisor slots 2
sup slot 0 4
sup slot 1 5
num of fabric slots 6
chassis family 1

Products

Connectrix, Connectrix MDS-Series, Connectrix MDS-9710-V2, Connectrix MDS-9718, Connectrix MDS-Series Firmware
Article Properties
Article Number: 000185047
Article Type: Solution
Last Modified: 09 أيار 2026
Version:  4
Find answers to your questions from other Dell users
Support Services
Check if your device is covered by Support Services.