PowerEdge: XE9680/XE9640/XE8640 Transient and peak load causing over current threshold alert in power supplies

Summary: The overcurrent threshold alert may be triggered on XE9680, XE9640, and XE8640 servers during transient peak load conditions.

This article applies to This article does not apply to This article is not tied to any specific product. Not all product versions are identified in this article.

Symptoms

Transient heavy workloads such as NVIDIA Data Center GPU Manager (DCGM) tests may stop responding.

No alerts are logged in the standard level of the System Event Log (SEL) or LifeCycle Controller (LC) log.

Cause

Over current settings in the Power Supply Unit (PSU) must be adjusted.

Resolution

Update power supply firmware:
For Liteon 2800W 54V PSU (DPN: NCMPF, 9NT8P) to version 00.08.08https://www.dell.com/support/home/en-us/drivers/driversdetails?driverid=yxhcp
For AEI 2800W 54V PSU (DPN: FX9WJ) to version 00.0D.12https://www.dell.com/support/home/en-us/drivers/driversdetails?driverid=g8kw5
For Delta 2800W 54V PSU (DPN: 1PDR6) to version 00.0BFChttps://www.dell.com/support/home/en-us/drivers/driversdetails?driverid=9c8h5