PowerFlex: System Shutdown Due to Critical System Inlet Temperature Alert
Summary: A power‑off occurs when the inlet temperature exceeds the critical limit because the alert action is configured to shut down; the temperature condition itself does not trigger an automatic shutdown. ...
This article applies to
This article does not apply to
This article is not tied to any specific product.
Not all product versions are identified in this article.
Symptoms
- The server receives a shutdown request after the critical system inlet threshold alert is triggered in the SEL
2020-11-22 17:58:52 |
10567 |
SYS1001 |
The system is turning off. |
2020-11-22 17:58:52 |
10566 |
SYS1003 |
System CPU Resetting |
2020-11-22 17:58:49 |
10565 |
ISM0007 |
The iDRAC Service Module communication with iDRAC has ended. |
2020-11-22 17:58:47 |
10564 |
RAC0704 |
Requested system powerdown |
2020-11-22 17:58:44 |
10563 |
TMP0121 |
The system inlet temperature is greater than the upper critical threshold. |
Cause
- The shutdown is triggered by iDRAC as the critical temperature alert action was set to 'Power Off'.
- The System Inlet Temperature will not proactively shut down the system.
Resolution
- The recommended setting is 'No Action'.
- The setting can be changed using UI or racadm.
- UI: Configuration > System Settings > Alert Configuration > Alerts > Alert Configuration > "Enclosure Temp Probe" or "Temperature"
- racadm :
racadm eventfilters set -c idrac.alert.system.tmp.critical -a none -n ipmi, snmp