PowerFlex: System Shutdown Due to Critical System Inlet Temperature Alert

Summary: A power‑off occurs when the inlet temperature exceeds the critical limit because the alert action is configured to shut down; the temperature condition itself does not trigger an automatic shutdown. ...

This article applies to This article does not apply to This article is not tied to any specific product. Not all product versions are identified in this article.

Symptoms

  •  The server receives a shutdown request after the critical system inlet threshold alert is triggered in the SEL

 

2020-11-22 17:58:52 10567 SYS1001 The system is turning off.
2020-11-22 17:58:52 10566 SYS1003 System CPU Resetting
2020-11-22 17:58:49 10565 ISM0007 The iDRAC Service Module communication with iDRAC has ended.
2020-11-22 17:58:47 10564 RAC0704 Requested system powerdown
2020-11-22 17:58:44 10563 TMP0121 The system inlet temperature is greater than the upper critical threshold.

Cause

  • The shutdown is triggered by iDRAC as the critical temperature alert action was set to 'Power Off'.  
  • The System Inlet Temperature will not proactively shut down the system.


temperature  

 
 

Resolution

  • The recommended setting is 'No Action'.
  • The setting can be changed using UI or racadm.
  • UI: Configuration > System Settings > Alert Configuration > Alerts > Alert Configuration > "Enclosure Temp Probe" or "Temperature"
  • racadm :
    racadm eventfilters set -c idrac.alert.system.tmp.critical -a none -n ipmi, snmp

Affected Products

Hyper-converged Systems
Article Properties
Article Number: 000181231
Article Type: Solution
Last Modified: 11 May 2026
Version:  3