Dell EMC PowerEdge MX740c Technical Specifications
Expanded operating temperature
| Expanded operating temperature | Specifications |
|---|---|
| Continuous Operation | 5°C–40°C at 5% to 85% RH with 29°C dew point
NOTE Outside the standard operating temperature (10°C–35°C), the system can operate continuously in temperatures as low as 5°C and as high as 40°C.
For temperatures 35°C–40°C, derate maximum allowable dry bulb temperature by 1°C per 175 m above 950 m (1°F per 319 ft). |
| Less than or equal to 1% of annual operating hours | –5°C–45°C at 5% to 90% RH with 29°C dew point
NOTE Outside the standard operating temperature (10°C–35°C), the system can operate down to –5°C or up to 45°C for a maximum of 1% of its annual operating hours.
For temperatures 40°C–45°C, derate maximum allowable temperature by 1°C per 125 m above 950 m (1°F per 228 ft). |
NOTE When operating in the expanded temperature range, system performance may be impacted.
NOTE When operating in the expanded temperature range, ambient temperature warnings maybe reported
on the LCD panel and in the System event log.
Expanded operating temperature restrictions
- Do not perform a cold startup below 5°C.
- The operating temperature that is specified is for a maximum altitude of 3050 m(10,000 ft).
- Low core count processors [Gold 6146,6144,6134,6128,5222,5217,5122] and higher wattage processors [Thermal Design Power (TDP)>140 W] are not supported.
- Non-Dell qualified peripheral cards or peripheral cards greater than 30 W are not supported.
- PCIe SSD is not supported.
- NVDIMM are not supported.
- DCPMMs are not supported.