Dell EMC PowerEdge MX740c Technical Specifications
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous contamination
. If the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may must rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
| Particulate contamination | Specifications |
|---|---|
| Air filtration | Data center air filtration as defined by ISO Class
8 per ISO 14644-1 with a 95% upper confidence limit. NOTE This condition applies
to data center environments only. Air filtration requirements do not
apply to IT equipment designed to be used outside a data center, in
environments such as an office or factory floor. NOTE Air entering the data
center must have MERV11 or MERV13 filtration. |
| Conductive dust | Air must be free of conductive dust, zinc whiskers,
or other conductive particles. NOTE This condition applies to data center and nondata center environments. |
| Corrosive dust |
NOTE This condition applies to data center and nondata center environments. |
| Gaseous contamination | Specifications |
|---|---|
| Copper coupon corrosion rate | <300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985. |
| Silver coupon corrosion rate | <200 Å/month as defined by AHSRAE TC9.9. |
NOTE Maximum
corrosive contaminant levels measured at ≤50% relative humidity.