
Dell EMC PowerEdge T340 Technical Specifications
Particulate and gaseous contamination specifications
The following
table defines the limitations that help avoid any damages to
the IT equipment and/or, or both failure from particulate and gaseous contamination.
If the levels of particulate or gaseous pollution exceed the specified
limitations and results in equipment damage or failure, you must rectify the environmental conditions. Remediation of environmental
conditions is the responsibility of the customer.
| Particulate contamination | Specifications |
|---|---|
| Air filtration | Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit. NOTE This condition
applies to data center environments only. Air filtration requirements
do not apply to IT equipment designed to be used outside a data center,
in environments such as an office or factory floor. NOTE Air entering the data
center must have MERV11 or MERV13 filtration. |
Conductive dust |
Air must be free of conductive dust, zinc whiskers, or other conductive particles. NOTE This condition applies
to data center and non-data center environments. |
Corrosive dust |
NOTE This condition
applies to data center and non-data center environments. |
| Gaseous contamination | Specifications |
|---|---|
| Copper Coupon Corrosion | <300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985. |
| Silver Coupon Corrosion | <200 Å/month as defined by AHSRAE TC9.9. |
NOTE Maximum
corrosive contaminant levels measured at ≤50% relative humidity.
Please provide ratings (1-5 stars).
Please provide ratings (1-5 stars).
Please provide ratings (1-5 stars).
Please select whether the article was helpful or not.
Comments cannot contain these special characters: <>()\