NOTE: For additional information
about environmental measurements for specific system configurations,
see
dell.com/environmental_datasheets.
|
Temperature
|
|
|
Maximum Temperature Gradient (Operating
and Storage)
|
20 °C/h (36 °F/h) |
|
Storage Temperature Limits |
–40 °C to 65 °C (–40 °F to 149 °F) |
Temperature
(Continuous Operation)
|
|
Temperature Ranges (for altitude less
than 950 m or 3117 ft)
|
10 °C to 35 °C (50 °F to 95 °F) with
no direct sunlight on the equipment.
|
|
Humidity Percentage Range |
10% to 80% Relative Humidity with 26
°C (78.8 °F) maximum dew point.
|
Relative
Humidity
|
|
|
Storage |
5% to 95% RH with 33 °C (91 °F) maximum
dew point. Atmosphere must be non-condensing at all times.
|
Maximum
Vibration
|
|
|
Operating |
0.26 G
rms at 5 Hz to 350 Hz
(all operation orientations).
|
|
Storage |
1.87 G
rms at 10 Hz to 500
Hz for 15 min (all six sides tested).
|
Maximum
Shock
|
|
|
Operating |
One shock pulse in the positive z axis
of 31 G for 2.6 ms in all operational orientations.
|
|
Storage |
Six consecutively executed shock pulses
in the positive and negative x, y, and z axes (one pulse on each side
of the system) of 71 G for up to 2 ms.
|
Maximum
Altitude
|
|
|
Operating |
3,048 m (
10,000 ft)
|
|
Storage |
12,000 m (39,370 ft). |
Operating
Altitude De-rating
|
|
Up to 35 °C (95 °F) |
Maximum temperature is reduced by 1 °C/300
m (1 °F/547 ft) above 950 m (3,117 ft).
|
|
35 °C to 40 °C (95 °F to 104 °F) |
Maximum temperature is reduced by 1 °C/175
m (1 °F/319 ft) above 950 m (3,117 ft).
|
|
40 °C to 45 °C (104 °F to 113 °F) |
Maximum temperature is reduced by 1 °C/125
m (1 °F/228 ft) above 950 m (3,117 ft).
|
Particulate
Contamination
-
NOTE: This section defines the limits to help avoid IT equipment damage
and/or failure from particulates and gaseous contamination. If it
is determined that levels of particulates or gaseous pollution are
beyond the limits specified below and are the reason for the damage
and/or failures to your equipment, it may be necessary for you to
re-mediate the environmental conditions that are causing the damage
and/or failures. Re-mediation of environmental conditions will be
the responsibility of the customer.
|
|
Air Filtration
-
NOTE: Applies to data center
environments only. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in environments
such as an office or factory floor.
|
Data center air filtration as defined
by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
-
NOTE: Air entering the data
center must have MERV11 or MERV13 filtration.
|
|
Conductive Dust
-
NOTE: Applies to data center
and non-data center environments.
|
Air must be free of conductive dust,
zinc whiskers, or other conductive particles.
|
|
Corrosive Dust
-
NOTE: Applies to data center
and non-data center environments.
|
- Air must be free of corrosive dust.
- Residual dust present in the air must have a deliquescent point
less than 60% relative humidity.
|
Gaseous
Contamination
|
-
NOTE: Maximum corrosive contaminant
levels measured at ≤50% relative humidity.
|
|
Copper Coupon Corrosion Rate |
<300 Å/month per Class G1 as defined
by ANSI/ISA71.04-1985.
|
|
Silver Coupon Corrosion Rate |
<200 Å/month as defined by AHSRAE
TC9.9.
|