Dell PowerEdge R7525 Installation and Service Manual
Installing the drive backplane
Prerequisites
- Follow the safety guidelines listed in the Safety instructions.
- Follow the procedure listed in the Before working inside your system.
- Remove the backplane cover.
- If installed,remove the air shroud.
- Remove all the drives.
- Remove the cooling fan cage assembly.
NOTE:To avoid damaging the backplane, ensure to move the control panel cables from the cable routing clips before removing the backplane.
NOTE:Route the cable properly when you replace it to prevent the cable from being pinched or crimped.
Steps
- Use the guides on the system as guides to align the slots on the backplane.
- Insert the backplane into the guides and lower the backplane until the blue release tabs clicks into place.
- Route the cables properly through the cable guide and connect the cables to the connector on the system board.
Figure 1. Installing the drive backplane 
Next steps
- Install the cooling fan cage assembly.
- Install all the drives.
- If removed, install the air shroud.
- Install the drive backplane cover.
- Connect the drive backplane cables to the connector on the system board.
- Connect the drive backplane cables to the connector on the backplane.
- Follow the procedure listed in After working inside your system.