Dell Technologies 14th Generation PowerEdge Server Troubleshooting Guide
Dell cooling problems
The fans are running at a higher speed than expected.
Prerequisites
NOTE:The fan number is referenced by the management software of the system. In the event of a problem with a particular fan, you can easily identify and replace it by noting down the fan numbers on the cooling fan assembly.
About this task
- The fan installed is not compatible with the server
- Ambient temperature is higher than the system specific ambient temperature
- External airflow is obstructed
- System cover, cooling shroud, EMI filler panel, memory module blank, or back filler bracket is missing or not installed properly
- The fans are not seated properly
- One or more fans are not functioning
- iDRAC failure on the motherboard
Recommended action
Steps
-
Update the iDRAC firmware and system BIOS to the latest version and clear the system event logs (SEL).
NOTE:System reboot is required for the BIOS update.
For more information about updating BIOS and firmware, see your systems documentation at dell.com/support.
- Ensure that the system chassis is closed and all expansion card slots and bay covers are in place.
- Check the internal system fans for obstructions and verify that all fans are spinning properly.
- Reseat or swap any failing fans with a known-good fan, and replace the fan if a known-good fan works. If a known-good fan does not work, replace the system board.