Dell EMC PowerEdge M640 Installation and Service Manual
Particulate and gaseous contamination specifications
The following
table defines the limitations that help avoid any equipment damage
or failure from particulates and gaseous contamination. If the levels
of particulates or gaseous pollution exceed the specified limitations
and result in equipment damage or failure, you may need to rectify
the environmental conditions. Re-mediation of environmental conditions
is the responsibility of the customer.
| Gaseous contamination | Specifications |
|---|---|
| Copper coupon corrosion rate | <300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985. |
| Silver coupon corrosion rate | <200 Å/month as defined by AHSRAE TC9.9. |