PSU specifications
The
PowerEdge
R740xd system supports up to two AC or DC power supply units (PSUs).
Table 1. PSU specifications
The table below are the specifications for 495 W, 750 W, 1100 W, 1600 W, 2000 W and 2400 W power supplies:
PSU
|
Class
|
Heat dissipation (maximum)
|
Frequency
|
Voltage
|
High line 200v240 V
|
Low line 100– 140 V
|
DC
|
Current
|
495 W AC
|
Platinum
|
1908 BTU/hr
|
50/60 Hz
|
100–240 V AC, autoranging
|
495 W
|
495 W
|
NA
|
6.5 A–3 A
|
750 W AC
|
Platinum
|
2891 BTU/hr
|
50/60 Hz
|
100–240 V AC, autoranging
|
750 W
|
750 W
|
NA
|
10 A–5 A
|
750 W AC
|
Titanium
|
2843 BTU/hr
|
50/60 Hz
|
200–240 V AC, autoranging
|
750 W
|
|
NA
|
5 A
|
750 W Mixed Mode HVDC (for China only)
|
Platinum
|
2891 BTU/hr
|
50/60 Hz
|
100–240 V AC, autoranging
|
750 W
|
750 W
|
NA
|
10 A–5 A
|
Platinum
|
2891 BTU/hr
|
N/A
|
240 V DC, autoranging
|
NA
|
NA
|
750W
|
4.5 A
|
750 W Mixed Mode
|
Platinum
|
2891 BTU/hr
|
50/60 Hz
|
100–240 V AC, autoranging
|
750 W
|
750 W
|
NA
|
10 A–5 A
|
Platinum(For China only)
|
2891 BTU/hr
|
N/A
|
240 V DC, autoranging
|
NA
|
NA
|
750 W
|
5 A
|
1100 W AC
|
Platinum
|
4100 BTU/hr
|
50/60 Hz
|
100–240 V AC, autoranging
|
1100 W
|
1050 W
|
|
12 A–6.5 A
|
1100 W DC
|
N/A
|
4416 BTU/hr
|
N/A
|
–(48 V to –60 V) DC, autoranging
|
NA
|
NA
|
1100 W
|
32 A
|
1100 W Mixed Mode HVDC (for China and Japan only)
|
Platinum
|
4100 BTU/hr
|
50/60 Hz
|
100–240 V AC, autoranging
|
1100 W
|
1050 W
|
|
12 A–6.5 A
|
N/A
|
4100 BTU/hr
|
N/A
|
200–380 V DC, autoranging
|
NA
|
NA
|
1100 W
|
6.4 A–3.2 A
|
1600 W AC
|
Platinum
|
6000 BTU/hr
|
50/60 Hz
|
100–240 V AC, autoranging
|
1600 W
|
800 W
|
NA
|
10 A
|
2000 W AC
|
Platinum
|
7500 BTU/hr
|
50/60 Hz
|
100–240 V AC, autoranging
|
2000 W
|
1000 W
|
NA
|
11.5 A
|
2400 W AC
|
Platinum
|
9000 BTU/hr
|
50/60 Hz
|
100–240 V AC, autoranging
|
2400 W
|
1400 W
|
NA
|
16 A
|
NOTE: Heat dissipation is calculated using the PSU wattage rating.
NOTE: This system is also designed to connect to the IT power systems with a phase to phase voltage not exceeding 240 V.
NOTE: PSUs rated for 1100 W Mixed Mode HVDC or 1100 W AC and higher require high-line voltage (200–240 V AC) to supply their rated capacity.