Dell DD and PowerProtect Hardware 8.0 Features and Specifications
Power requiremements
The input current, power (VA), and dissipation per enclosure listed in this document are based on measurements of fully configured enclosures under worst-case operating conditions. Use the operating maximum values to plan the configuration of your storage system. These values represent either:
- the values for a single power supply line cord, or
- the sum of the values shared by the line cords of the combined power supplies in the same enclosure, with the division between the line cords and supplies at the current sharing ratio (approximately 50% each).
A failure of one of the combined power supplies per enclosure results in the remaining power supply supporting the full load. You must use a rackmount cabinet or rack with appropriate power distribution, and have main branch AC distribution that can handle these values for each enclosure in the cabinet.
| Requirement | Description |
|---|---|
| AC line voltage | 100 to 240V AC ± 10%, single-phase, 47 to 63 Hz |
| AC line current (operating maximum) | 2.9 A max at 100V AC |
| 1.6 A max at 200V AC | |
| Power consumption (operating maximum) | 287 VA (281 W) max at 100V AC |
| 313 VA (277 W) max at 200V AC | |
| Power factor | 0.9 min at full load at 100V AC |
| 0.9 min at full load at 200V AC | |
| Heat dissipation (operating maximum) | 1.01 x 106 J/hr (959 Btu/hr) max at 100V AC |
| 1.01 x 106 J/hr (945 Btu/hr) max at 200V AC | |
| In-rush current | 30 A max for ½ line cycle, per line cord at 240V AC |
| Startup surge current | 25 A peak max per line cord, max at any line voltage |
| AC protection | 10 A fuse on each power supply, both Line and Neutral |
| AC inlet type | IEC320-C14 appliance coupler, per power zone |
| Ride-through time | 30 ms min |
| Current sharing | Droop Load Sharing |
|
NOTE:
|
|
| Requirement | Description |
|---|---|
| DC line voltage | -39 to -72V DC (nominal -48 or -60 V power systems) |
| DC line current (operating maximum) | 7.92 A max at -39V DC |
| 6.43 A max at -48V DC | |
| 4.39 A max at -72V DC | |
| Power consumption (operating maximum) | 309 W max at -39V DC |
| 309 W max at -48V DC | |
| 316 W max at -72V DC | |
| Heat dissipation (operating maximum) | 1.11 x 106 J/hr (1054 Btu/hr) max at -39V DC |
| 1.11 x 106 J/hr (1054 Btu/hr) max at -48V DC | |
| 1.14 x 106 J/hr (1078 Btu/hr) max at -72V DC | |
| In-rush current | 20 A peak per requirements in EN300 132-2 Sect 4.7 limit curve |
| DC protection | 20 A fuse in each power supply |
| DC inlet type | Positronics PLB3W3M1000 |
| Mating DC connector | Positronics PLB3W3F7100A1 |
| Positronics Inc. | |
| http://www.connectpositronic.com | |
| Ride-through time | 5 ms min. (test condition: Vin = -40V DC) |
| Current sharing | Droop Load Sharing |
|