PowerEdge Servers Error and Event Messages Reference Guide
LCPO—Liquid Cooling System Default Action UnGraceful Power Off Event Messages
LCPO001
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- A small leak is detected on the arg1 arg2.
- Arguments
- arg1 = DeviceType
- arg2 = DeviceInstance
- Detailed Description
- A small leak is detected on the device identified in the message.
- Recommended Response Action
- 1) Disconnect the input power to the server. 2) Disconnect the server liquid hoses from the rack manifold. 3) If the issue persists, Collect a SupportAssist collection (TSR) report using iDRAC. Visit https://www.dell.com/support/incidents-online/contactus/dynamic to use the Virtual Assistant to analyze the collection and recommend a resolution.
- Category
- System Health (LCPO = Liquid Cooling System Default Action UnGraceful Power Off)
- Severity
- Warning
- Trap/EventID
- 3786
- LCD Message
- A small leak is detected on the <DeviceType> <DeviceInstance>.
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Graceful Power OFF
- Applicable Event or Alert Types
- CMC—Not Applicable
LCPO003
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- A large leak is detected on the arg1 arg2.
- Arguments
- arg1 = DeviceType
- arg2 = DeviceInstance
- Detailed Description
- A large leak is detected on the device identified in the message.
- Recommended Response Action
- 1) Disconnect the input power to the server. 2) Disconnect the server liquid hoses from the rack manifold. 3) If the issue persists, Collect a SupportAssist collection (TSR) report using iDRAC. Visit https://www.dell.com/support/incidents-online/contactus/dynamic to use the Virtual Assistant to analyze the collection and recommend a resolution.
- Category
- System Health (LCPO = Liquid Cooling System Default Action UnGraceful Power Off)
- Severity
- Critical
- Trap/EventID
- 3785
- LCD Message
- A large leak is detected on the <DeviceType> <DeviceInstance>.
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Graceful Power OFF
- Applicable Event or Alert Types
- CMC—Not Applicable
LCPO008
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- A leak is detected on arg1 arg2.
- Arguments
- arg1 = DeviceType
- arg2 = DeviceInstance
- Detailed Description
- A leak has been detected on the system. There is an issue with the liquid cooling system.
- Recommended Response Action
- Remove system input power and disconnect server liquid hoses from the rack manifold.
- Category
- System Health (LCPO = Liquid Cooling System Default Action UnGraceful Power Off)
- Severity
- Critical
- Trap/EventID
- 3785
- LCD Message
- A leak is detected on <DeviceType> <DeviceInstance>
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Graceful Power OFF
- Applicable Event or Alert Types
- CMC—Not Applicable
LCPO009
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The arg1 detected a leak on arg2 in the rack with Service Tag arg3.
- Arguments
- arg1 = DeviceType
- arg2 = DeviceInstance
- arg3 = Rack_ServiceTag
- Detailed Description
- A coolant leakage issue was detected in the device available in the rack identified in the message.
- Recommended Response Action
- Do the following: 1) Locate the rack. 2) Press the leak button in the IRC to indicate leak acknowledgement. 3) Visually identify if there is a coolant leak. 4) If there is a visible coolant leak, perform leak remediation as described in the Installation and Service Manual (ISM) of the Integrated Rack model on the support site.
- Category
- System Health (LCPO = Liquid Cooling System Default Action UnGraceful Power Off)
- Severity
- Critical
- Trap/EventID
- 3785
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCPO101
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- A small leak is detected by the peer node.
- Detailed Description
- A small leak is detected by the peer node.
- Recommended Response Action
- 1) Disconnect the power cords. 2) Disconnect the liquid hose pipes of the server from the rack manifold 3) If the issue persists, Collect a SupportAssist collection (TSR) report using iDRAC. Visit https://www.dell.com/support/incidents-online/contactus/dynamic to use the Virtual Assistant to analyze the collection and recommend a resolution.
- Category
- System Health (LCPO = Liquid Cooling System Default Action UnGraceful Power Off)
- Severity
- Warning
- Trap/EventID
- 3786
- LCD Message
- A small leak is detected by the peer node.
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Graceful Power OFF
- Applicable Event or Alert Types
- CMC—Not Applicable
LCPO103
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- A large leak is detected by the peer node.
- Detailed Description
- A large leak is detected by the peer node.
- Recommended Response Action
- 1) Disconnect the power cords. 2) Disconnect the liquid hose pipes of the server from the rack manifold 3) If the issue persists, Collect a SupportAssist collection (TSR) report using iDRAC. Visit https://www.dell.com/support/incidents-online/contactus/dynamic to use the Virtual Assistant to analyze the collection and recommend a resolution.
- Category
- System Health (LCPO = Liquid Cooling System Default Action UnGraceful Power Off)
- Severity
- Critical
- Trap/EventID
- 3785
- LCD Message
- A large leak is detected by the peer node.
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Graceful Power OFF
- Applicable Event or Alert Types
- CMC—Not Applicable
Please provide ratings (1-5 stars).
Please provide ratings (1-5 stars).
Please provide ratings (1-5 stars).
Please select whether the article was helpful or not.
Comments cannot contain these special characters: <>()\