LCR—Liquid Cooling Rack Event Messages

LCR0001

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
IRC has Opened Valve:arg1.
Arguments
  • arg1 = valveID
Detailed Description
The valve identified by the given ID is in the open position.
Recommended Response Action
No response action is required.
Category
Audit (LCR = Liquid Cooling Rack)
Severity
Informational
Trap/EventID
9947
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0002

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
IRC has Closed Valve:arg1.
Arguments
  • arg1 = valveID
Detailed Description
The valve identified by the given ID is in the closed position.
Recommended Response Action
No response action is required.
Category
Audit (LCR = Liquid Cooling Rack)
Severity
Informational
Trap/EventID
9947
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0003

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
IRC failed to Open Valve:arg1, current position at arg2 percent open, target position is arg3 percent open.
Arguments
  • arg1 = valveID
  • arg2 = percentNum
  • arg3 = percentNum
Detailed Description
This error occurs when IRC is unable to change the valve position. Need to check the valve when this error occurs.
Recommended Response Action
The affected valve needs immediate attention from on-site staff. Check the valves to make sure they are not stuck, turned off or malfunctioning.
Category
System Health (LCR = Liquid Cooling Rack)
Severity
Critical
Trap/EventID
3801
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0004

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
IRC failed to Open Valve:arg1, current position at arg2 percent open.
Arguments
  • arg1 = valveID
  • arg2 = percentNum
Detailed Description
The valve identified by the given ID failed to update position.
Recommended Response Action
The affected valve needs immediate attention from on-site staff. Check the valves to make sure they are not stuck, turned off or malfunctioning.
Category
System Health (LCR = Liquid Cooling Rack)
Severity
Critical
Trap/EventID
3801
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0005

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
IRC failed to Close Valve:arg1, current position at arg2 percent open.
Arguments
  • arg1 = valveID
  • arg2 = percentNum
Detailed Description
The valve identified by the given ID failed to update position.
Recommended Response Action
The affected valve needs immediate attention from on-site staff. Check the valves to make sure they are not stuck, turned off or malfunctioning.
Category
System Health (LCR = Liquid Cooling Rack)
Severity
Critical
Trap/EventID
3801
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0006

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
IRC is Opening Valve:arg1.
Arguments
  • arg1 = valveID
Detailed Description
To update users that valve position was not updated.
Recommended Response Action
No response action is required.
Category
Audit (LCR = Liquid Cooling Rack)
Severity
Informational
Trap/EventID
9947
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0007

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
IRC has Closed Valve:arg1.
Arguments
  • arg1 = valveID
Detailed Description
IRC is closing Valve.
Recommended Response Action
No response action is required.
Category
Audit (LCR = Liquid Cooling Rack)
Severity
Informational
Trap/EventID
9947
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0008

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
Valve:arg1 received an invalid position request:arg2. Valid positions are 0 or 100. No action performed.
Arguments
  • arg1 = valveID
  • arg2 = positionNum
Detailed Description
The valve position request is invalid, thus valve position will not updated.
Recommended Response Action
Set a position using one of the permitted values: 0 or 100, corresponding to 0 percent open and 100 percent open respectively.
Category
System Health (LCR = Liquid Cooling Rack)
Severity
Warning
Trap/EventID
3802
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0009

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
Failed to read position feedback for Valve:arg1.
Arguments
  • arg1 = valveID
Detailed Description
IRC could not read position of the Valve.
Recommended Response Action
The affected valve needs immediate attention from on-site staff. Check the valves to make sure they are not stuck, turned off or malfunctioning.
Category
System Health (LCR = Liquid Cooling Rack)
Severity
Warning
Trap/EventID
3802
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0010

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The valve type was not detected for Valve:arg1. Valve control is currently unavailable.
Arguments
  • arg1 = valveID
Detailed Description
IRC could not read the Device Type of the Valve after it was Hot Plugged in. Valve cannot be controlled.
Recommended Response Action
The affected valve needs immediate attention from on-site staff. Check the valves to make sure they are not stuck, turned off or malfunctioning.
Category
System Health (LCR = Liquid Cooling Rack)
Severity
Warning
Trap/EventID
3802
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0011

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The Valve:arg1 is disconnected.
Arguments
  • arg1 = valveID
Detailed Description
The valve identified by the provided ID was disconnected.
Recommended Response Action
The affected valve needs immediate attention from on-site staff. Check the valves to make sure they are not stuck, turned off or malfunctioning.
Category
Audit (LCR = Liquid Cooling Rack)
Severity
Warning
Trap/EventID
9946
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0012

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The Valve:arg1 is connected.
Arguments
  • arg1 = valveID
Detailed Description
The valve identified by the provided ID was disconnected.
Recommended Response Action
No response action is required.
Category
Audit (LCR = Liquid Cooling Rack)
Severity
Informational
Trap/EventID
9947
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0013

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The valve arg1 is not moving and stuck in an incorrect position.
Arguments
  • arg1 = valueNumber
Detailed Description
The valve identified by the provided ID is not moving and is in the wrong position.
Recommended Response Action
The affected valve requires attention. Check for any mechanical obstruction that could impede the turning off the valve. If the issue persists, refer to the Users Guide of the product model available in the support site.
Category
System Health (LCR = Liquid Cooling Rack)
Severity
Critical
Trap/EventID
3801
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0014

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The Valve:arg1 has power fault.
Arguments
  • arg1 = valveID
Detailed Description
The valve identified in the message has a power-related issue.
Recommended Response Action
The affected valve requires attention. Check that the cable to the valve is properly and fully connected at both ends. If the issue persists, refer to the Users Guide of the product model available in the support site.
Category
System Health (LCR = Liquid Cooling Rack)
Severity
Critical
Trap/EventID
3801
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0015

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The Valve:arg1 is already set to position arg2. No action performed.
Arguments
  • arg1 = valveID
  • arg2 = positionNum
Detailed Description
The valve position request is the current position, thus valve position will not be updated.
Recommended Response Action
No response action is required.
Category
Audit (LCR = Liquid Cooling Rack)
Severity
Informational
Trap/EventID
9947
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0016

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
Valve arg1 is currently updating its position. Please wait for the transition to complete, then submit a new position request.
Arguments
  • arg1 = valveID
Detailed Description
The valve is updating position, thus any new position request will not be accepted.
Recommended Response Action
Try setting a new position request after the valve has finished transitioning.
Category
Audit (LCR = Liquid Cooling Rack)
Severity
Informational
Trap/EventID
9947
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCR0017

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The eRDHx valve position is arg1. The current position of the value is arg2.
Arguments
  • arg1 = valveStatus
  • arg2 = currentPosition
Detailed Description
The Enclosed Rear Door Heat Exchanger (eRDHx) valve position is as identified in the message including the position value identified in the message. Position may be opened, closed, or partially opened. Value may be any number from 0 to 100.
Recommended Response Action
No response action is required.
Category
Audit (LCR = Liquid Cooling Rack)
Severity
Informational
Trap/EventID
9947
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable