PowerEdge Servers Error and Event Messages Reference Guide
LCR—Liquid Cooling Rack Event Messages
LCR0001
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- IRC has Opened Valve:arg1.
- Arguments
- arg1 = valveID
- Detailed Description
- The valve identified by the given ID is in the open position.
- Recommended Response Action
- No response action is required.
- Category
- Audit (LCR = Liquid Cooling Rack)
- Severity
- Informational
- Trap/EventID
- 9947
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0002
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- IRC has Closed Valve:arg1.
- Arguments
- arg1 = valveID
- Detailed Description
- The valve identified by the given ID is in the closed position.
- Recommended Response Action
- No response action is required.
- Category
- Audit (LCR = Liquid Cooling Rack)
- Severity
- Informational
- Trap/EventID
- 9947
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0003
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- IRC failed to Open Valve:arg1, current position at arg2 percent open, target position is arg3 percent open.
- Arguments
- arg1 = valveID
- arg2 = percentNum
- arg3 = percentNum
- Detailed Description
- This error occurs when IRC is unable to change the valve position. Need to check the valve when this error occurs.
- Recommended Response Action
- The affected valve needs immediate attention from on-site staff. Check the valves to make sure they are not stuck, turned off or malfunctioning.
- Category
- System Health (LCR = Liquid Cooling Rack)
- Severity
- Critical
- Trap/EventID
- 3801
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0004
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- IRC failed to Open Valve:arg1, current position at arg2 percent open.
- Arguments
- arg1 = valveID
- arg2 = percentNum
- Detailed Description
- The valve identified by the given ID failed to update position.
- Recommended Response Action
- The affected valve needs immediate attention from on-site staff. Check the valves to make sure they are not stuck, turned off or malfunctioning.
- Category
- System Health (LCR = Liquid Cooling Rack)
- Severity
- Critical
- Trap/EventID
- 3801
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0005
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- IRC failed to Close Valve:arg1, current position at arg2 percent open.
- Arguments
- arg1 = valveID
- arg2 = percentNum
- Detailed Description
- The valve identified by the given ID failed to update position.
- Recommended Response Action
- The affected valve needs immediate attention from on-site staff. Check the valves to make sure they are not stuck, turned off or malfunctioning.
- Category
- System Health (LCR = Liquid Cooling Rack)
- Severity
- Critical
- Trap/EventID
- 3801
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0006
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- IRC is Opening Valve:arg1.
- Arguments
- arg1 = valveID
- Detailed Description
- To update users that valve position was not updated.
- Recommended Response Action
- No response action is required.
- Category
- Audit (LCR = Liquid Cooling Rack)
- Severity
- Informational
- Trap/EventID
- 9947
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0007
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- IRC has Closed Valve:arg1.
- Arguments
- arg1 = valveID
- Detailed Description
- IRC is closing Valve.
- Recommended Response Action
- No response action is required.
- Category
- Audit (LCR = Liquid Cooling Rack)
- Severity
- Informational
- Trap/EventID
- 9947
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0008
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- Valve:arg1 received an invalid position request:arg2. Valid positions are 0 or 100. No action performed.
- Arguments
- arg1 = valveID
- arg2 = positionNum
- Detailed Description
- The valve position request is invalid, thus valve position will not updated.
- Recommended Response Action
- Set a position using one of the permitted values: 0 or 100, corresponding to 0 percent open and 100 percent open respectively.
- Category
- System Health (LCR = Liquid Cooling Rack)
- Severity
- Warning
- Trap/EventID
- 3802
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0009
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- Failed to read position feedback for Valve:arg1.
- Arguments
- arg1 = valveID
- Detailed Description
- IRC could not read position of the Valve.
- Recommended Response Action
- The affected valve needs immediate attention from on-site staff. Check the valves to make sure they are not stuck, turned off or malfunctioning.
- Category
- System Health (LCR = Liquid Cooling Rack)
- Severity
- Warning
- Trap/EventID
- 3802
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0010
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The valve type was not detected for Valve:arg1. Valve control is currently unavailable.
- Arguments
- arg1 = valveID
- Detailed Description
- IRC could not read the Device Type of the Valve after it was Hot Plugged in. Valve cannot be controlled.
- Recommended Response Action
- The affected valve needs immediate attention from on-site staff. Check the valves to make sure they are not stuck, turned off or malfunctioning.
- Category
- System Health (LCR = Liquid Cooling Rack)
- Severity
- Warning
- Trap/EventID
- 3802
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0011
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The Valve:arg1 is disconnected.
- Arguments
- arg1 = valveID
- Detailed Description
- The valve identified by the provided ID was disconnected.
- Recommended Response Action
- The affected valve needs immediate attention from on-site staff. Check the valves to make sure they are not stuck, turned off or malfunctioning.
- Category
- Audit (LCR = Liquid Cooling Rack)
- Severity
- Warning
- Trap/EventID
- 9946
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0012
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The Valve:arg1 is connected.
- Arguments
- arg1 = valveID
- Detailed Description
- The valve identified by the provided ID was disconnected.
- Recommended Response Action
- No response action is required.
- Category
- Audit (LCR = Liquid Cooling Rack)
- Severity
- Informational
- Trap/EventID
- 9947
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0013
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The valve arg1 is not moving and stuck in an incorrect position.
- Arguments
- arg1 = valueNumber
- Detailed Description
- The valve identified by the provided ID is not moving and is in the wrong position.
- Recommended Response Action
- The affected valve requires attention. Check for any mechanical obstruction that could impede the turning off the valve. If the issue persists, refer to the Users Guide of the product model available in the support site.
- Category
- System Health (LCR = Liquid Cooling Rack)
- Severity
- Critical
- Trap/EventID
- 3801
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0014
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The Valve:arg1 has power fault.
- Arguments
- arg1 = valveID
- Detailed Description
- The valve identified in the message has a power-related issue.
- Recommended Response Action
- The affected valve requires attention. Check that the cable to the valve is properly and fully connected at both ends. If the issue persists, refer to the Users Guide of the product model available in the support site.
- Category
- System Health (LCR = Liquid Cooling Rack)
- Severity
- Critical
- Trap/EventID
- 3801
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0015
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The Valve:arg1 is already set to position arg2. No action performed.
- Arguments
- arg1 = valveID
- arg2 = positionNum
- Detailed Description
- The valve position request is the current position, thus valve position will not be updated.
- Recommended Response Action
- No response action is required.
- Category
- Audit (LCR = Liquid Cooling Rack)
- Severity
- Informational
- Trap/EventID
- 9947
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0016
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- Valve arg1 is currently updating its position. Please wait for the transition to complete, then submit a new position request.
- Arguments
- arg1 = valveID
- Detailed Description
- The valve is updating position, thus any new position request will not be accepted.
- Recommended Response Action
- Try setting a new position request after the valve has finished transitioning.
- Category
- Audit (LCR = Liquid Cooling Rack)
- Severity
- Informational
- Trap/EventID
- 9947
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCR0017
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The eRDHx valve position is arg1. The current position of the value is arg2.
- Arguments
- arg1 = valveStatus
- arg2 = currentPosition
- Detailed Description
- The Enclosed Rear Door Heat Exchanger (eRDHx) valve position is as identified in the message including the position value identified in the message. Position may be opened, closed, or partially opened. Value may be any number from 0 to 100.
- Recommended Response Action
- No response action is required.
- Category
- Audit (LCR = Liquid Cooling Rack)
- Severity
- Informational
- Trap/EventID
- 9947
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
Please provide ratings (1-5 stars).
Please provide ratings (1-5 stars).
Please provide ratings (1-5 stars).
Please select whether the article was helpful or not.
Comments cannot contain these special characters: <>()\