PowerEdge Servers Error and Event Messages Reference Guide

PDF

RDHX—Rear Door Heat Exchanger Event Messages

RDHX0001

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
arg1 value has dropped below the lower critical limit.
Arguments
  • arg1 = sensorName
Detailed Description
To update the user that the sensor value is less than the lower critical threshold.
Recommended Response Action
Inspect the sensor in described in the message.
Category
System Health (RDHX = Rear Door Heat Exchanger)
Severity
Critical
Trap/EventID
3817
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

RDHX0002

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
arg1 value has exceeded the upper critical limit.
Arguments
  • arg1 = sensorName
Detailed Description
To update the user that the sensor value is greater than the upper critical threshold.
Recommended Response Action
Inspect the sensor described in the message.
Category
System Health (RDHX = Rear Door Heat Exchanger)
Severity
Critical
Trap/EventID
3817
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

RDHX0003

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
arg1 value has dropped below the lower warning limit.
Arguments
  • arg1 = sensorName
Detailed Description
To update the user that the sensor value is less than the lower warning threshold.
Recommended Response Action
Inspect the sensor described in the message.
Category
System Health (RDHX = Rear Door Heat Exchanger)
Severity
Warning
Redfish Event Type
Alert
Applicable Event or Alert Types
No alerts are applicable for this message

RDHX0004

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
arg1 value has exceeded the upper warning limit.
Arguments
  • arg1 = sensorName
Detailed Description
To update the user that the sensor value is greater than the upper warning threshold.
Recommended Response Action
Inspect the sensor described in the message.
Category
System Health (RDHX = Rear Door Heat Exchanger)
Severity
Warning
Trap/EventID
3818
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

RDHX0005

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The arg1 value has returned to its normal value.
Arguments
  • arg1 = sensorName
Detailed Description
The value of the sensor described in the message has returned to normal value.
Recommended Response Action
No response action is required.
Category
Audit (RDHX = Rear Door Heat Exchanger)
Severity
Informational
Trap/EventID
9963
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

RDHX0006

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The Fan Test could not be run because the Enhanced Rear Door Heat Exchanger must be in the "Off" state.
Detailed Description
The Fan Test could not be run because the Enhanced Rear Door Heat Exchanger must be in the "Off" state.
Recommended Response Action
Transition the Enhanced Rear Door Heat Exchanger to the "Off" state.
Category
Audit (RDHX = Rear Door Heat Exchanger)
Severity
Warning
Trap/EventID
9962
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

RDHX0007

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
Fan Test is currently running. Try again when the Status property is set to Complete.
Detailed Description
Fan Test is currently running. Try again when the Status property is set to "Complete".
Recommended Response Action
Fan Test is currently running. Try again when the Status property is set to "Complete".
Category
Audit (RDHX = Rear Door Heat Exchanger)
Severity
Informational
Trap/EventID
9963
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

RDHX0008

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The arg1 has opened.
Arguments
  • arg1 = sourceName
Detailed Description
Door Opened. Please check the door.
Recommended Response Action
Door Opened. Please check the door.
Category
Audit (RDHX = Rear Door Heat Exchanger)
Severity
Informational
Trap/EventID
9963
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

RDHX0009

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The arg1 has closed.
Arguments
  • arg1 = sourceName
Detailed Description
The door described in the message has closed.
Recommended Response Action
No response action is required.
Category
Audit (RDHX = Rear Door Heat Exchanger)
Severity
Informational
Trap/EventID
9963
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

RDHX0011

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The eRDHx thermal controls are turned On.
Detailed Description
The eRDHx thermal controls are turned On. eRDHx fans are running, liquid cooling valve is open, and are now under thermal controls.
Recommended Response Action
No response action is required.
Category
Audit (RDHX = Rear Door Heat Exchanger)
Severity
Informational
Trap/EventID
9963
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

RDHX0012

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The eRDHx thermal controls are arg1.
Arguments
  • arg1 = Mode
Detailed Description
The eRDHx thermal controls are in the Mode indicated in the message. eRDHx fans are not running, liquid cooling valve is closed, effectively eRDHx is no longer cooling the rack.
Recommended Response Action
Immediate attention is needed if the current mode of eRDHx is not intentionally set. In this mode, eRDHx is no longer cooling the rack. All systems in the rack must be in power off state. This mode is intended for maintenance purpose only.
Category
Audit (RDHX = Rear Door Heat Exchanger)
Severity
Critical
Trap/EventID
9961
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

RDHX0013

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The eRDHx Power Recovery mode is set to thermal controls arg1.
Arguments
  • arg1 = ACRecoveryPowerState
Detailed Description
The eRDHx Power Recovery is set to the thermal controls mode identified in the message.
Recommended Response Action
The eRDHx power recovery is set to the thermal controls mode identified in the message. The mode should match the power recovery of the systems in the rack to avoid risk of thermal events.
Category
Audit (RDHX = Rear Door Heat Exchanger)
Severity
Informational
Trap/EventID
9963
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

RDHX0014

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The eRDHx is connected to IRC.
Detailed Description
The Enclosed Rear Door Heat Exchanger (eRDHx) is connected to IRC.
Recommended Response Action
No response action is required.
Category
Audit (RDHX = Rear Door Heat Exchanger)
Severity
Informational
Trap/EventID
9963
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

RDHX0015

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The eRDHx is arg1.
Arguments
  • arg1 = connection_state
Detailed Description
The Enclosed Rear Door Heat Exchanger (eRDHx) is in a state as indicated in the message.
Recommended Response Action
Immediate attention is needed if the state of eRDHx as indicated in the message is not expected. eRDHx may be in a state where it is no longer providing cooling to the rack. Locate the rack and inspect the connection. For further instructions, refer to the Integrated Rack Controller Installation and Service Manual available on the support site.
Category
Audit (RDHX = Rear Door Heat Exchanger)
Severity
Warning
Trap/EventID
9962
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable