PowerEdge Servers Error and Event Messages Reference Guide

PDF

LCS—Liquid Cooling System Event Messages

LCS0001

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
A small leak is detected on the arg1 arg2.
Arguments
  • arg1 = DeviceType
  • arg2 = DeviceInstance
Detailed Description
A small leak is detected on the device identified in the message.
Recommended Response Action
1) Disconnect the power cords. 2) Disconnect the liquid hose pipes of the server from the rack manifold 3) If the issue persists, Collect a SupportAssist collection (TSR) report using iDRAC. Visit https://www.dell.com/support/incidents-online/contactus/dynamic to use the Virtual Assistant to analyze the collection and recommend a resolution.
Category
System Health (LCS = Liquid Cooling System)
Severity
Warning
Trap/EventID
3050
LCD Message
A small leak is detected on the <DeviceType> <DeviceInstance>.
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Power Cycle, Reset
Applicable Event or Alert Types
CMC—Not Applicable

LCS0002

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
A small leak that was earlier detected on the device is now resolved.
Detailed Description
A small leak that was earlier detected on the device is now resolved.
Recommended Response Action
No response action is required.
Category
System Health (LCS = Liquid Cooling System)
Severity
Informational
Trap/EventID
3051
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Power Cycle, Reset
Applicable Event or Alert Types
CMC—Not Applicable

LCS0003

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
A large leak is detected on the arg1 arg2.
Arguments
  • arg1 = DeviceType
  • arg2 = DeviceInstance
Detailed Description
A large leak is detected on the device identified in the message.
Recommended Response Action
1) Disconnect the power cords. 2) Disconnect the liquid hose pipes of the server from the rack manifold 3) If the issue persists, Collect a SupportAssist collection (TSR) report using iDRAC. Visit https://www.dell.com/support/incidents-online/contactus/dynamic to use the Virtual Assistant to analyze the collection and recommend a resolution.
Category
System Health (LCS = Liquid Cooling System)
Severity
Critical
Trap/EventID
3049
LCD Message
A large leak is detected on the <DeviceType> <DeviceInstance>.
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Power Cycle, Reset
Applicable Event or Alert Types
CMC—Not Applicable

LCS0004

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
An error is detected in the leak detection sensor of the arg1.
Arguments
  • arg1 = DeviceType
Detailed Description
An error is detected in the leak detection sensor of the device identified in the message. There is no functional leak detection.
Recommended Response Action
If the issue persists, Collect a SupportAssist collection (TSR) report using iDRAC. Visit https://www.dell.com/support/incidents-online/contactus/dynamic to use the Virtual Assistant to analyze the collection and recommend a resolution.
Category
System Health (LCS = Liquid Cooling System)
Severity
Warning
LCD Message
Leak Sensor error detected on <DeviceType>.
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*, LCD
Applicable Event or Alert Types
CMC—Not Applicable

LCS0005

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
An error that occurred in the leak detection sensor is now resolved.
Detailed Description
An error that occurred in the leak detection sensor is now resolved.
Recommended Response Action
No response action is required.
Category
System Health (LCS = Liquid Cooling System)
Severity
Informational
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*, LCD
Applicable Event or Alert Types
CMC—Not Applicable

LCS0006

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
User arg1 liquid cooling leak detection reporting using IPMI interface.
Arguments
  • arg1 = action
Detailed Description
User requested state or configuration change using specified interface.
Recommended Response Action
No response action is required.
Category
Configuration (LCS = Liquid Cooling System)
Severity
Informational
Redfish Event Type
Not Applicable
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCS0007

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
A large leak that was earlier detected on the device is now resolved.
Detailed Description
A large leak that was earlier detected on the device is now resolved.
Recommended Response Action
No response action is required.
Category
System Health (LCS = Liquid Cooling System)
Severity
Informational
Trap/EventID
3051
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Power Cycle, Reset
Applicable Event or Alert Types
CMC—Not Applicable

LCS0008

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
A leak is detected on arg1 arg2.
Arguments
  • arg1 = DeviceType
  • arg2 = DeviceInstance
Detailed Description
A leak has been detected on the system. There is an issue with the liquid cooling system.
Recommended Response Action
Remove system input power and disconnect server liquid hoses from the rack manifold.
Category
System Health (LCS = Liquid Cooling System)
Severity
Critical
Trap/EventID
3049
LCD Message
A leak is detected on <DeviceType> <DeviceInstance>
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Reset
Applicable Event or Alert Types
CMC—Not Applicable

LCS0009

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The health of the Liquid Cooling pump arg1 is critical.
Arguments
  • arg1 = number
Detailed Description
The Liquid cooling pump is not performing optimally. The liquid pipe maybe installed improperly or there is a leak in the liquid pipe.
Recommended Response Action
If the issue persists, Collect a SupportAssist collection (TSR) report using iDRAC. Visit https://www.dell.com/support/incidents-online/contactus/dynamic to use the Virtual Assistant to analyze the collection and recommend a resolution.
Category
System Health (LCS = Liquid Cooling System)
Severity
Critical
Redfish Event Type
Not Applicable
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCS0010

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The health of the Liquid Cooling pump arg1 is normal.
Arguments
  • arg1 = number
Detailed Description
The Liquid cooling pump is working normally. An error that occurred in the Liquid cooling pump is now resolved.
Recommended Response Action
No response action is required.
Category
System Health (LCS = Liquid Cooling System)
Severity
Informational
Redfish Event Type
Not Applicable
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCS0011

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The leak sensor: arg1 is reporting a healthy status.
Arguments
  • arg1 = DeviceInstance
Detailed Description
The specific leak sensor identified in the message is reporting a healthy status.
Recommended Response Action
No response action is required.
Category
System Health (LCS = Liquid Cooling System)
Severity
Informational
Redfish Event Type
Alert
Applicable Event or Alert Types
No alerts are applicable for this message

LCS0013

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
An error is detected in the leak detection sensor of the arg1.
Arguments
  • arg1 = DeviceInstance
Detailed Description
An error is detected in the leak detection sensor of the device identified in the message. There is no functional leak detection.
Recommended Response Action
Do the following: 1) Locate the rack. 2) Locate the sensor identified in the message. 3) Inspect the sensor as described in the Installation and Service Manual (ISM) of the Integrated Rack model on the support site.
Category
System Health (LCS = Liquid Cooling System)
Severity
Warning
Trap/EventID
3050
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
Applicable Event or Alert Types
CMC—Not Applicable

LCS1002

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
A small leak detected by the peer node is now resolved.
Detailed Description
A small leak detected by the peer node is now resolved.
Recommended Response Action
No response action is required.
Category
System Health (LCS = Liquid Cooling System)
Severity
Informational
Trap/EventID
3051
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, OS Log
Applicable Event or Alert Types
CMC—Not Applicable

LCS1007

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
A large leak detected by the peer node is now resolved.
Detailed Description
A large leak detected by the peer node is now resolved.
Recommended Response Action
No response action is required.
Category
System Health (LCS = Liquid Cooling System)
Severity
Informational
Trap/EventID
3051
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, OS Log
Applicable Event or Alert Types
CMC—Not Applicable

LCS2000

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The arg1 detected arg2 arg3.
Arguments
  • arg1 = DeviceName
  • arg2 = LeakType
  • arg3 = Location
Detailed Description
Leak detection sensor reported a status change.
Recommended Response Action
To resolve the issue, verify the lifecycle log data and initiate necessary corrective actions.
Category
System Health (LCS = Liquid Cooling System)
Severity
Informational
Trap/EventID
3051
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, OS Log
Applicable Event or Alert Types
CMC—Not Applicable

LCS2001

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The arg1 is connected.
Arguments
  • arg1 = device
Detailed Description
Leak detection sensor is connected.
Recommended Response Action
No response action is required.
Category
System Health (LCS = Liquid Cooling System)
Severity
Informational
Trap/EventID
3051
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, OS Log
Applicable Event or Alert Types
CMC—Not Applicable

LCS2002

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The arg1 leak detection sensor is disconnected.
Arguments
  • arg1 = sensorName
Detailed Description
The leak detection sensor identified in the message is disconnected.
Recommended Response Action
If leak sensor disconnection is not expected, locate the rack and inspect the specific sensor indicated in the message. Ensure the cable is connected fully and properly. For more information see the Installation and Service Manual (ISM) specific to the device model available on the support site.
Category
System Health (LCS = Liquid Cooling System)
Severity
Warning
Trap/EventID
3050
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, OS Log
Applicable Event or Alert Types
CMC—Not Applicable

LCS2003

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The Liquid Cooling Leak Power On policy is modified. Changing the default configuration value may void the product warranty if a genuine leak occurs and powering on is allowed.
Detailed Description
The Liquid Cooling Leak Power On policy is modified. Changing the default configuration value may void the product warranty if a genuine leak occurs and powering on is allowed.
Recommended Response Action
If the change to default configuration was unintentional, revert to the default settings of leak detection power-on policy.
Category
Audit (LCS = Liquid Cooling System)
Severity
Warning
Trap/EventID
9194
LCD Message
The Liquid Cooling Leak Power On policy is modified. Changing the default configuration value may void the product warranty if a genuine leak occurs and powering on is allowed.
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log
Applicable Event or Alert Types
CMC—Not Applicable

LCS2004

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The Liquid Cooling Leak Power On policy is modified. The server Power On operation is not permitted when a liquid cooling leak is detected.
Detailed Description
The Liquid Cooling Leak Power On policy is modified. The server Power On operation is not permitted when a liquid cooling leak is detected.
Recommended Response Action
No response action is required.
Category
Audit (LCS = Liquid Cooling System)
Severity
Informational
Trap/EventID
9195
LCD Message
The Liquid Cooling Leak Power On policy is modified. The server Power On operation is not permitted when a liquid cooling leak is detected.
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log
Applicable Event or Alert Types
CMC—Not Applicable

LCS2005

NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the Applicable Event or Alert Types section.
Message
The Liquid Cooling Leak Power On policy is modified. The server Power On operation is permitted when a liquid cooling leak is detected.
Detailed Description
The Liquid Cooling Leak Power On policy is modified. The server Power On operation is permitted when a liquid cooling leak is detected.
Recommended Response Action
No response action is required.
Category
Audit (LCS = Liquid Cooling System)
Severity
Informational
Trap/EventID
9195
LCD Message
The Liquid Cooling Leak Power On policy is modified. The server Power On operation is permitted when a liquid cooling leak is detected.
Redfish Event Type
Alert
Applicable Event or Alert Types
iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log
Applicable Event or Alert Types
CMC—Not Applicable

Rate this content

Accurate
Useful
Easy to understand
Was this article helpful?
0/3000 characters
  Please provide ratings (1-5 stars).
  Please provide ratings (1-5 stars).
  Please provide ratings (1-5 stars).
  Please select whether the article was helpful or not.
  Comments cannot contain these special characters: <>()\