PowerEdge Servers Error and Event Messages Reference Guide
LCS—Liquid Cooling System Event Messages
LCS0001
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- A small leak is detected on the arg1 arg2.
- Arguments
- arg1 = DeviceType
- arg2 = DeviceInstance
- Detailed Description
- A small leak is detected on the device identified in the message.
- Recommended Response Action
- 1) Disconnect the power cords. 2) Disconnect the liquid hose pipes of the server from the rack manifold 3) If the issue persists, Collect a SupportAssist collection (TSR) report using iDRAC. Visit https://www.dell.com/support/incidents-online/contactus/dynamic to use the Virtual Assistant to analyze the collection and recommend a resolution.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Warning
- Trap/EventID
- 3050
- LCD Message
- A small leak is detected on the <DeviceType> <DeviceInstance>.
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Power Cycle, Reset
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS0002
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- A small leak that was earlier detected on the device is now resolved.
- Detailed Description
- A small leak that was earlier detected on the device is now resolved.
- Recommended Response Action
- No response action is required.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Informational
- Trap/EventID
- 3051
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Power Cycle, Reset
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS0003
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- A large leak is detected on the arg1 arg2.
- Arguments
- arg1 = DeviceType
- arg2 = DeviceInstance
- Detailed Description
- A large leak is detected on the device identified in the message.
- Recommended Response Action
- 1) Disconnect the power cords. 2) Disconnect the liquid hose pipes of the server from the rack manifold 3) If the issue persists, Collect a SupportAssist collection (TSR) report using iDRAC. Visit https://www.dell.com/support/incidents-online/contactus/dynamic to use the Virtual Assistant to analyze the collection and recommend a resolution.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Critical
- Trap/EventID
- 3049
- LCD Message
- A large leak is detected on the <DeviceType> <DeviceInstance>.
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Power Cycle, Reset
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS0004
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- An error is detected in the leak detection sensor of the arg1.
- Arguments
- arg1 = DeviceType
- Detailed Description
- An error is detected in the leak detection sensor of the device identified in the message. There is no functional leak detection.
- Recommended Response Action
- If the issue persists, Collect a SupportAssist collection (TSR) report using iDRAC. Visit https://www.dell.com/support/incidents-online/contactus/dynamic to use the Virtual Assistant to analyze the collection and recommend a resolution.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Warning
- LCD Message
- Leak Sensor error detected on <DeviceType>.
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*, LCD
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS0005
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- An error that occurred in the leak detection sensor is now resolved.
- Detailed Description
- An error that occurred in the leak detection sensor is now resolved.
- Recommended Response Action
- No response action is required.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Informational
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*, LCD
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS0006
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- User arg1 liquid cooling leak detection reporting using IPMI interface.
- Arguments
- arg1 = action
- Detailed Description
- User requested state or configuration change using specified interface.
- Recommended Response Action
- No response action is required.
- Category
- Configuration (LCS = Liquid Cooling System)
- Severity
- Informational
- Redfish Event Type
- Not Applicable
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS0007
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- A large leak that was earlier detected on the device is now resolved.
- Detailed Description
- A large leak that was earlier detected on the device is now resolved.
- Recommended Response Action
- No response action is required.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Informational
- Trap/EventID
- 3051
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Power Cycle, Reset
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS0008
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- A leak is detected on arg1 arg2.
- Arguments
- arg1 = DeviceType
- arg2 = DeviceInstance
- Detailed Description
- A leak has been detected on the system. There is an issue with the liquid cooling system.
- Recommended Response Action
- Remove system input power and disconnect server liquid hoses from the rack manifold.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Critical
- Trap/EventID
- 3049
- LCD Message
- A leak is detected on <DeviceType> <DeviceInstance>
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log, Power Off, Reset
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS0009
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The health of the Liquid Cooling pump arg1 is critical.
- Arguments
- arg1 = number
- Detailed Description
- The Liquid cooling pump is not performing optimally. The liquid pipe maybe installed improperly or there is a leak in the liquid pipe.
- Recommended Response Action
- If the issue persists, Collect a SupportAssist collection (TSR) report using iDRAC. Visit https://www.dell.com/support/incidents-online/contactus/dynamic to use the Virtual Assistant to analyze the collection and recommend a resolution.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Critical
- Redfish Event Type
- Not Applicable
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS0010
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The health of the Liquid Cooling pump arg1 is normal.
- Arguments
- arg1 = number
- Detailed Description
- The Liquid cooling pump is working normally. An error that occurred in the Liquid cooling pump is now resolved.
- Recommended Response Action
- No response action is required.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Informational
- Redfish Event Type
- Not Applicable
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS0011
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The leak sensor: arg1 is reporting a healthy status.
- Arguments
- arg1 = DeviceInstance
- Detailed Description
- The specific leak sensor identified in the message is reporting a healthy status.
- Recommended Response Action
- No response action is required.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Informational
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- No alerts are applicable for this message
LCS0013
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- An error is detected in the leak detection sensor of the arg1.
- Arguments
- arg1 = DeviceInstance
- Detailed Description
- An error is detected in the leak detection sensor of the device identified in the message. There is no functional leak detection.
- Recommended Response Action
- Do the following: 1) Locate the rack. 2) Locate the sensor identified in the message. 3) Inspect the sensor as described in the Installation and Service Manual (ISM) of the Integrated Rack model on the support site.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Warning
- Trap/EventID
- 3050
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, Remote System Log, Redfish Eventing*, LC Log*
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS1002
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- A small leak detected by the peer node is now resolved.
- Detailed Description
- A small leak detected by the peer node is now resolved.
- Recommended Response Action
- No response action is required.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Informational
- Trap/EventID
- 3051
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, OS Log
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS1007
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- A large leak detected by the peer node is now resolved.
- Detailed Description
- A large leak detected by the peer node is now resolved.
- Recommended Response Action
- No response action is required.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Informational
- Trap/EventID
- 3051
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, OS Log
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS2000
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The arg1 detected arg2 arg3.
- Arguments
- arg1 = DeviceName
- arg2 = LeakType
- arg3 = Location
- Detailed Description
- Leak detection sensor reported a status change.
- Recommended Response Action
- To resolve the issue, verify the lifecycle log data and initiate necessary corrective actions.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Informational
- Trap/EventID
- 3051
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, OS Log
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS2001
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The arg1 is connected.
- Arguments
- arg1 = device
- Detailed Description
- Leak detection sensor is connected.
- Recommended Response Action
- No response action is required.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Informational
- Trap/EventID
- 3051
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, OS Log
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS2002
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The arg1 leak detection sensor is disconnected.
- Arguments
- arg1 = sensorName
- Detailed Description
- The leak detection sensor identified in the message is disconnected.
- Recommended Response Action
- If leak sensor disconnection is not expected, locate the rack and inspect the specific sensor indicated in the message. Ensure the cable is connected fully and properly. For more information see the Installation and Service Manual (ISM) specific to the device model available on the support site.
- Category
- System Health (LCS = Liquid Cooling System)
- Severity
- Warning
- Trap/EventID
- 3050
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, OS Log
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS2003
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The Liquid Cooling Leak Power On policy is modified. Changing the default configuration value may void the product warranty if a genuine leak occurs and powering on is allowed.
- Detailed Description
- The Liquid Cooling Leak Power On policy is modified. Changing the default configuration value may void the product warranty if a genuine leak occurs and powering on is allowed.
- Recommended Response Action
- If the change to default configuration was unintentional, revert to the default settings of leak detection power-on policy.
- Category
- Audit (LCS = Liquid Cooling System)
- Severity
- Warning
- Trap/EventID
- 9194
- LCD Message
- The Liquid Cooling Leak Power On policy is modified. Changing the default configuration value may void the product warranty if a genuine leak occurs and powering on is allowed.
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS2004
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The Liquid Cooling Leak Power On policy is modified. The server Power On operation is not permitted when a liquid cooling leak is detected.
- Detailed Description
- The Liquid Cooling Leak Power On policy is modified. The server Power On operation is not permitted when a liquid cooling leak is detected.
- Recommended Response Action
- No response action is required.
- Category
- Audit (LCS = Liquid Cooling System)
- Severity
- Informational
- Trap/EventID
- 9195
- LCD Message
- The Liquid Cooling Leak Power On policy is modified. The server Power On operation is not permitted when a liquid cooling leak is detected.
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log
- Applicable Event or Alert Types
- CMC—Not Applicable
LCS2005
NOTE: Event or Alert types that are enabled by default are identified using an asterisk (*) symbol in the
Applicable Event or Alert Types section.
- Message
- The Liquid Cooling Leak Power On policy is modified. The server Power On operation is permitted when a liquid cooling leak is detected.
- Detailed Description
- The Liquid Cooling Leak Power On policy is modified. The server Power On operation is permitted when a liquid cooling leak is detected.
- Recommended Response Action
- No response action is required.
- Category
- Audit (LCS = Liquid Cooling System)
- Severity
- Informational
- Trap/EventID
- 9195
- LCD Message
- The Liquid Cooling Leak Power On policy is modified. The server Power On operation is permitted when a liquid cooling leak is detected.
- Redfish Event Type
- Alert
- Applicable Event or Alert Types
- iDRAC—Filter Visibility, IPMI Alert*, SNMP Alert, Email Alert, Remote System Log, WS Eventing, Redfish Eventing*, LC Log*, LCD, OS Log
- Applicable Event or Alert Types
- CMC—Not Applicable