Dell PowerEdge XR4000r Installation and Service Manual
PSU specifications
The PowerEdge XR4000r system supports up to two AC or DC power supply units (PSUs).
| PSU | Class | Heat dissipation (maximum) (BTU/hr) | Frequency (Hz) | Voltage | AC | DC | Current (A) | |
|---|---|---|---|---|---|---|---|---|
| High line 200–240 V | Low line 100–120 V | |||||||
| 1800W Mixed Mode | Titanium | 6750 BTU/hr | 50/60 Hz | 200 - 240 V AC | 1800W | NA | NA | 10A |
| NA | 6750 BTU/hr | NA | 240 V DC | NA | NA | 1800W | 8.2A | |
| 1400 W Mixed Mode | Platinum | 5250 BTU/hr | 50/60 Hz | 100 - 240 V AC | 1400 W | 1050 W | NA | 12 A - 8 A |
| NA | 5250 BTU/hr | NA | 240 V DC | NA | NA | 1400 W | 6.6 A | |
| 1400 W Mixed Mode | Titanium | 5250 BTU/hr | 50/60 Hz | 100 - 240 V AC | 1400 W | 1050 W | NA | 12 A - 8 A |
| NA | 5250 BTU/hr | NA | 240 V DC | NA | NA | 1400 W | 6.5 A | |
| 1100 W Mixed Mode | Titanium | 4100 BTU/hr | 50/60 Hz | 100 - 240 V AC | 1100 W | 1050 W | NA | 12 A - 6.3 A |
| NA | 4100 BTU/hr | NA | 240 V DC | NA | NA | 1100 W | 5.2 A | |
| 1100 W DC | NA | 4265 BTU/hr | NA | -48 -( -60) V | NA | NA | 1100 W | 27 A |
NOTE:This system is also designed to connect to the IT power systems with a phase-to-phase voltage not exceeding 240 V.
NOTE:Heat dissipation is calculated using the PSU wattage rating.
NOTE:When selecting or upgrading the system configuration, to ensure optimum power utilization, verify the system power consumption with the Enterprise Infrastructure Planning Tool available at
calc.