| ASHRAE A4 | Allowable continuous operations |
|---|---|
| Temperature Ranges (For Altitude <900 meters or 2953 feet) | 5°C-45°C (41°F-113°F) with no direct sunlight on the equipment |
| Humidity Percent Ranges (Non-Condensing at all times) | 8% RH with -12°C minimum dew point to 90% RH with 24°C (75.2°F) maximum dew point |
| Operational Altitude De-Rating | Maximum temperature is reduced by 1°C/125 meters (1.8°F/410 feet) above 900 meters (2,953 feet) |
| Rugged | Allowable continuous operations |
|---|---|
| Temperature Ranges (For Altitude <900 meters or 2953 feet) | -5°C-55°C (23°F-131°F) with no direct sunlight on the equipment |
| Humidity Percent Ranges (Non-Condensing at all times) | 8% RH with -12°C minimum dew point to 90% RH with 24°C (75.2°F) maximum dew point |
| Operational Altitude De-Rating | Maximum temperature is reduced by 1°C/80 meters (1.8°F/262 feet) above 900 meters (2,953 feet) |
| Allowable continuous operations | |
|---|---|
| Maximum Temperature Gradient (applies to both operation and non-operation) |
20°C in an hour* (36°F in an hour) and 5°C in 15 minutes (9°F in 15 minutes), 5°C in an hour* (9°F in an hour) for tape hardware |
| Non-Operational Temperature Limits | -40°C-65°C (-40°F-149°F) |
| Non-Operational Humidity Limits (Non-Condensing at all times) | 5% to 95% RH with 27°C (80.6°F) maximum dew point. |
| Maximum Non-Operational Altitude | 12,000 meters (39,370 feet) |
| Maximum Operational Altitude | 3,048 meters (10,000 feet) |