Use the alignment pegs on the board and the
alignment casings on the riser to position the riser over the connector.
Lower the riser into place until the riser
is fully seated in the connector.
Lower the blue latch to secure the riser to
the chassis.
Replace the cover on the
storage controller.
Remove the service baffle from the chassis.
CAUTION: To prevent a thermal shutdown of the
storage system, the
storage controller must
be installed within three minutes of removing the service baffle.
Install the
storage controller into
the chassis.
Reconnect the cables to the
storage controller.
Clear the
storage controller swap
status from the
Hardware tab in
Dell Storage Manager
.
For instructions, see the
Dell Storage Manager
Administrator’s
Guide
.
Next steps
Use
Dell Storage Manager
to edit
the
Storage Center settings and
set the operation mode of the
Storage Center to Production mode.
Use
Dell Storage Manager
to send
SupportAssist information to
technical support