Particulate
and gaseous contamination specifications
The following
table defines the limitations that help avoid any equipment damage
or failure from particulates and gaseous contamination. If the levels
of particulates or gaseous pollution exceed the specified limitations
and result in equipment damage or failure, you may need to rectify
the environmental conditions. Re-mediation of environmental conditions
is the responsibility of the customer.
NOTE: This section defines
the limits to help avoid IT equipment damage and/or failure from particulates
and gaseous contamination. If it is determined that levels of particulates
or gaseous pollution are beyond the limits specified in the following table and are
the reason for the damage and/or failures to your equipment, it may
be necessary for you to re-mediate the environmental conditions that
are causing the damage and/or failures. Re-mediation of environmental
conditions will be the responsibility of the customer.
Table 1. Particulate contamination specificationsAir filtration specification: Data center air filtration as
defined by ISO Class 8 per ISO 14644-1 shpuld have a 95% upper confidence
limit. Note: This condition applies only to data center environments.
Air filtration requirements do not apply to IT equipment designed
to be used outside a data center, in environments such as an office
or factory floor. Note: Air entering the data center must have MERV11
or MERV13 filtration. Conductive dust specification: Air must be free
of conductive dust, zinc whiskers, or other conductive particles.
Note: This condition applies to data center and non-data center environments.
Corrosive dust specification: Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less
than 60% relative humidity. Note: This condition applies to data center
and non-data center environments.
Particulate contamination
Specifications
Air Filtration
NOTE: Applies to data center environments only. Air filtration requirements
do not apply to IT equipment designed to be used outside a data center,
in environments such as an office or factory floor.
Data center air filtration as defined
by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
NOTE: Air entering the data
center must have MERV11 or MERV13 filtration.
Conductive Dust
NOTE: Applies to data center and non-data center environments.
Air must be free of conductive dust,
zinc whiskers, or other conductive particles.
Corrosive
Dust
NOTE: Applies to
data center and non-data center environments.
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
Table 2. Gaseous contamination specificationsThe copper coupon corrosion rate is <300 Å/month per Class
G1 as defined by ANSI/ISA71.04-1985. The silver coupon corrosion rate
is <200 Å/month as defined by AHSRAE TC9.9.
Gaseous contamination
Specifications
Copper Coupon Corrosion Rate
<300 Å/month per Class G1 as defined
by ANSI/ISA71.04-1985.
Silver
Coupon Corrosion Rate
<200 Å/month as defined by AHSRAE TC9.9.