PowerScale: One side of the PowerScale rack appears to be pulling more power than the other side
Summary: When reviewing Power Distribution Unit (PDU) load, a customer noticed that one side of the rack appeared to be pulling more power than the other side.
This article applies to
This article does not apply to
This article is not tied to any specific product.
Not all product versions are identified in this article.
Symptoms
Reviewing the rack power draw, there is an imbalance in power between the redundant PDUs the rack is connected to.
Cause
By default, PowerScale nodes use a HotSpare power supply configuration. One power supply is active; the second power supply runs in standby mode. At certain intervals, the node switches the power supply states to balance wear in the hardware.
This configuration is more energy efficient than running the power supplies in active/active mode.
Resolution
This is operating as designed, and nothing must be done. If data center requirements are that the nodes run in active/active configuration, contact support and provide this KB article number.
Affected Products
PowerScale F200, PowerScale F210, PowerScale F600, PowerScale F710, PowerScale F900, PowerScale F910Article Properties
Article Number: 000228376
Article Type: Solution
Last Modified: 06 Feb 2026
Version: 4