PowerScale OneFS: Event Notification: Power Supply Failure Detected in Switch xxxx on Int-x Fabric Event ID 200020009
Summary: OneFS: Event notification: Power supply failure detected in switch xxxx on int-xxx fabric (Event ID 200020009)
This article applies to
This article does not apply to
This article is not tied to any specific product.
Not all product versions are identified in this article.
Symptoms
Event
The following event notification (Event ID 200020009) is received. This event is generated when an internal Ethernet network switch for a cluster has detected a loss of power from one of the power supplies.Power supply failure detected in switch xxxx on int-xxx fabric
Cause
Details
This event notification is issued when one of the following conditions exists:- One of the power supplies in an internal network switch which is not providing power.
- The power provided from the electrical outlet to the power supply is insufficient.
Resolution
Response
Before you begin troubleshooting the issue, confirm that the event is not related to maintenance on the cluster. After confirming that no maintenance is in progress, proceed with the following troubleshooting.
- Determine if the electrical outlet is functioning properly by plugging the power cable into a different electrical outlet.
- If the issue is not resolved by using a different outlet, try a replacement power cable.
- If power is not restored to the switch, contact Isilon Technical Support for assistance.
Troubleshooting steps:
- Check for the switch details to connect to it with commands:
# isi_dump_fabric int-a # isi_dump_fabric int-b # python -c "import isi.net.backendmon.util as u; print (u.intuit_switch_addr(\"int-a\")); print (u.intuit_switch_addr(\"int-b\"))"
- Connect to the switch and check Power Supply Unit (PSU) status (Make a support case if assistance is required connecting to the switch)
- Dell switches are used for backend connection, Check the PSU status using the following command:
# show system example - OS10# show system Node Id : 1 MAC : e8:b5:d0:b8:f6:e9 Number of MACs : 640 Up Time : 63 weeks 4 days 22:00:02 ...snip hit enter for more until you see the PSU -- Power Supplies -- PSU-ID Status Type AirFlow Fan Speed(rpm) Status ---------------------------------------------------------------- 1 up AC REVERSE 1 13770 up 2 fail
- Open a Service Request on Switch Serial Number and send out a new PSU if the above output shows an issue.