ECS: Sistem Bir Düğümde Yüksek Sıcaklık Algıladı

Summary: Sistemin bir düğümde yüksek sıcaklık sensörü okuması algıladığını bildiren bir e-posta uyarısı alırsam neleri kontrol edebilirim?

This article applies to This article does not apply to This article is not tied to any specific product. Not all product versions are identified in this article.

Instructions

  1. Uyarı verilen düğümün hangi donanıma sahip olduğunu doğrulayın.

    admin@node1:~> sudo xdoctor -x
    Telegraf Version: 3.8.0.2-1549.73c8abc2
    Fabric Version: 3.8.0.2-4347.d30cd09
    Fabric-Zookeeper Version: 3.8.0.2-120.b4a1c5c
    Utilities Version: 3.7.0.4-1166.b78f3fe
    Influxdb Version: 3.8.0.2-1549.73c8abc2
    Grafana Version: 3.8.0.2-1549.73c8abc2
    Syslog Version: 3.8.0.2-4347.d30cd09
    Service Version: 9.0.0.0-22840.479b013c74
    Os Version: 3.8.0.2-2113.3fa664c.3
    Fluxd Version: 3.8.0.2-1549.73c8abc2
    Throttler Version: 3.8.0.2-1549.73c8abc2
    Object Image Version: 3.8.0.2-138636.7343cd5c2c3
    --------------------
    ECS Version: 3.8.0.2
    --------------------
    HW Gen  : 2
    HW Model: U-Series
    HW Code : S2600KP
    -------------------------
    xDoctor Version: 4.8-98.0
    -------------------------
    

    Gen 1/2 düğümleri için e-postadaki yardım gerektiğini belirten forma yanıt verin. 3. Nesil düğümler için bu KB'nin geri kalanını izleyin.

  2. Sıcaklık sensörlerinin mevcut durumunu kontrol edin. Aşağıda, düğümlerden ikisinde bu iki düğümde sorun olduğunu gösteren "CRIT" ifadesini görüyoruz. Tüm düğümler "Tamam" olarak rapor veriyorsa ancak bu uyarı son zamanlarda birkaç kez alındıysa bu, tekrarlanan bir sorun olabilir. Öyleyse, e-postadaki forma yinelenen bir sıcaklık uyarısı ile yardım gerektiğini yanıtlayın.

    admin@node1:~> viprexec -i  cs_hal sensors temp
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    Processor         Temperature         Temp              OK      53 Degrees Celsius
    Processor         Temperature         Temp              OK      53 Degrees Celsius
    System Board      Temperature         Inlet Temp        CRIT    40 Degrees Celsius; above critical threshold
    System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    Processor         Temperature         Temp              OK      47 Degrees Celsius
    Processor         Temperature         Temp              OK      49 Degrees Celsius
    System Board      Temperature         Inlet Temp        CRIT    39 Degrees Celsius; above critical threshold
    System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    Processor         Temperature         Temp              OK      46 Degrees Celsius
    Processor         Temperature         Temp              OK      46 Degrees Celsius
    System Board      Temperature         Inlet Temp        OK      35 Degrees Celsius
    System Board      Temperature         Exhaust Temp      OK      47 Degrees Celsius
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
    
    ...
    ...
    ...

    Birden fazla düğümün "iyi durumda olmadığı" bildirilirse bu durum, muhtemelen veri merkezinizin ortamıyla ilgili bir sorundur. ECS'nin bulunduğu alanda ECS sıcaklığını artırabilecek herhangi bir sorun olmadığından emin olun.

  3. ECS fanlarının durumunu kontrol edin.

    admin@ecs:~>cs_hal sensors fan
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    System Board      Fan                 Fan1              OK      12600 RPM
    System Board      Fan                 Fan2              OK      12600 RPM
    System Board      Fan                 Fan3              OK      16920 RPM
    System Board      Fan                 Fan4              OK      16800 RPM
    System Board      Fan                 Fan5              OK      17040 RPM
    System Board      Fan                 Fan6              OK      16920 RPM
    System Board      Fan                 Fan Redundancy    OK      fully redundant;
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
  4. Hem sıcaklık sensörü çıkışları hem de fan çıkışları dahil olmak üzere yardımın gerekli olduğu e-postadaki formu yanıtlayın.

 