NOTE: Your system is capable
of 40 °C and 45 °C excursion operation for fresh air cooled data centers.
For more information, see the Owner's Manual.
-
NOTE: For additional information
about environmental measurements for specific system configurations,
see
dell.com/environmental_datasheets.
|
Temperature
|
|
|
Operating |
Continuous operation: 10 °C to 35 °C.
De-rate maximum allowable dry bulb temperature at 1 °C/300 m above
900 m (1°F /550 ft).
-
NOTE: For information on supported expanded operating temperature range
and configurations, see
support.dell.com/manuals.
|
|
Storage |
–40 °C to 65 °C (–40 °F to 149 °F) with
a maximum temperature gradation of 20 °C per hour.
|
Relative
humidity
|
|
|
Operating |
10% to 80% relative humidity (RH), with
26 °C maximum dew point.
|
|
Storage |
5% to 95% relative humidity ambient with
33 °C (91 °F) maximum dew point.
|
Maximum
vibration
|
|
|
Operating |
0.26 Grms at 5 Hz to 350 Hz (all operation
orientations).
|
|
Storage |
1.87 Grms at 10 Hz to 500 Hz for 15 min
(all six sides tested).
|
Maximum
shock
|
|
|
Operating |
One shock pulse in the positive z axis
(one pulse on each side of the system) of 31 G for 2.6 ms in the operational
orientation.
|
|
Storage |
Six consecutively executed shock pulses
in the positive and negative x, y, and z axes (one pulse on each side
of the system) of 71 G for up to 2 ms.
Six consecutively executed
shock pulses in the positive and negative x, y, and z axes (one pulse
on each side of the system) of 22 G faired square wave pulse with
velocity change at 200 inches/second (508 centimeters/second).
|
Altitude
|
|
|
Operating |
–15.2 m to
3048 m (–50 to
10,000 ft).
-
NOTE: For altitudes above
2950 ft, the maximum operating temperature is derated 1 ºF/550 ft.
|
|
Storage |
–15.2 m to 10,668 m (–50 ft to 35,000
ft).
|
Airborne
contaminant level
|
|
Class |
G1 as defined by ISA-S71.04-1985. |