How is site power quality determined

Summary: The purpose of this document is to provide a means whereby the site power quality can be determined for use with electronic computing equipment.

This article applies to This article does not apply to This article is not tied to any specific product. Not all product versions are identified in this article.

Symptoms

Certain Dell computers (such as Dell PowerEdge servers) are designed to work in accordance with electric specifications defined by the IEEE organization. The following information may be used to determine if the site power is within the IEEE standard for use with computing equipment:

Minimal site power requirements according to the IEEE Std 518-1982:

  • Frequency within +/- 0.5Hz. (This varies from country or region to country or region. See Table 1, below, for the country-specific information.)
  • Steady-state voltage within +/-8% of normal-rated voltage. (This varies from country or region to country or region. Refer to Table 1, below, for the country-specific information.)
  • Transient voltage conditions not exceeding +15% or -18% nominal, and returning to normal voltage within 0.5 seconds.
  • Total harmonic voltage distortion not exceeding 5%.
In order to verify the quality of the site power, a licensed electrician with equipment that can detect the above conditions are required.
 
NOTE: An example of such equipment would be a Dranetz Power Platform 4300 line analyzer.

World-Wide AC Voltages
Voltage Country or region
100V 60Hz Japan, Okinawa
100V 50Hz Japan
110V 60Hz Belize, Brazil, Colombia, Dominican Republic, Ecuador, Guam, Guyana, Haiti, Honduras, Panama, Peru, Philippines, Taiwan
110V 50Hz Azores, Belgium, Bolivia, France, Guyana, Haiti, Jamaica, Lebanon, Somalia, Turkey
115V 60Hz Brazil, El Salvador, Netherlands Antilles, Panama, Philippines, Surinam, Trinidad and Tobago, Barbados, Bolivia, France
115V 50Hz Barbados, Bolivia, France
120V 60Hz American Samoa, Bahamas, Bermuda, Brazil, Canada, Cayman Islands, Colombia, Costa Rica, Ecuador, Guam, Guatemala, Haiti, Liberia, Netherlands Antilles, Nicaragua, Okinawa, Puerto Rico, Venezuela, Virgin Islands (American)
120V 50Hz Cambodia, France, Luxembourg, Venezuela, Vietnam
125V 60Hz Brazil
125V 50Hz France, Indonesia
126V 60Hz Panama
127V 60Hz Brazil, Ecuador, Mexico, Netherlands Antilles, Saudi Arabia, Tahiti
127V 50Hz Algeria, Belgium, Brazil, Cameroon, Canary Islands, France, Italy, Libya, Madagascar, Mallorca Island, Monaco, Morocco, Netherlands Antilles, Senegal, Spain, Surinam, Togo, Tunisia, Vietnam
130V 50Hz Belgium
150V 60Hz Colombia
200V 50Hz Hong Kong
220V 60Hz Afghanistan, Belize, Brazil, Peru
220V 50Hz Afghanistan, Algeria, Angola, Argentina, Austria, Azores, Bangladesh, Belgium, Benin, Bolivia, Botswana, Bulgaria, Burundi, Cambodia, Cameroon, Canary Islands, Cape Verde, Central African Republic, Chad, Chile, China (P.R.), Congo, Czech Republic, Denmark, Djibouti, Egypt, Equatorial Guinea, Ethiopia, Faeroe Islands, Finland, France, French Guiana, Gabon, Gambia, German D.R., Fed. Rep of Germany, Ghana, Greece, Greenland, Guadeloupe, Guinea, Guinea-Bissau, Hungary, Iceland, India, Indonesia, Iraq, Ireland, Italy, Ivory Coast, Jerusalem, Jordan, Laos, Lebanon, Lesotho, Luxembourg, Macau, Madagascar, Madeira, Mallorca Island, Mali, Martinique, Monaco, Morocco, Mozambique, Nepal, Netherlands, Netherlands Antilles, New Caledonia, Niger, Paraguay, Peru, Poland, Portugal, Romania, Russia, Rwanda, Saudi Arabia, Somalia, South Africa, Spain, Sweden, Switzerland, Thailand, Togo, Tunisia, Turkey, the former USSR, United Arab Emirates, United Kingdom (Northern Ireland), Upper Volta, Uruguay, Vietnam, Yemen (Arab Rep.), Yugoslavia, Zaire, Zambia, Zimbabwe.
230V 60Hz Antigua, Bahrain, Brazil, St. Kitts and Nevis, Trinidad and Tobago
230V 50Hz Bahrain, Bolivia, Belgium, Burma, Cameroon, Channel Islands, Dominica, France, Grenada, India, Israel, Libya, Malawi, Malaysia, Maldives, Mauritius, Montserrat, New Zealand, Nigeria, Norway, Pakistan, St. Vincent, Saudi Arabia, Sierra Leone, Singapore, Somalia, South Africa, Sri Lanka, Swaziland, Tanzania, United Arab Emirates, United Kingdom (Northern Ireland), Western Samoa, Yemen (Aden), Zimbabwe
240V 60Hz American Samoa
240V 50Hz Australia, Channel Islands, Cyprus, Fiji, Gibraltar, Isle of Man, Kenya, Kuwait, Malaysia, Malta, Oman, Papua, Qatar, St. Lucia, Seychelles, South Africa, Tonga, Uganda, United Arab Emirates, United Kingdom (England, Scotland, Wales)
250V 50Hz Australia, South Africa
Table 1 - World-Wide AC Voltages
 