ECS: Systém zjistil vysokou teplotu v uzlu
Summary: Co mohu zkontrolovat, pokud obdržím e-mailovou výstrahu s informací, že systém zjistil snímač vysoké teploty, který čte na uzlu.
Instructions
-
Ověřte, o jaký hardware se jedná upozorňovaný uzel.
admin@node1:~> sudo xdoctor -x Telegraf Version: 3.8.0.2-1549.73c8abc2 Fabric Version: 3.8.0.2-4347.d30cd09 Fabric-Zookeeper Version: 3.8.0.2-120.b4a1c5c Utilities Version: 3.7.0.4-1166.b78f3fe Influxdb Version: 3.8.0.2-1549.73c8abc2 Grafana Version: 3.8.0.2-1549.73c8abc2 Syslog Version: 3.8.0.2-4347.d30cd09 Service Version: 9.0.0.0-22840.479b013c74 Os Version: 3.8.0.2-2113.3fa664c.3 Fluxd Version: 3.8.0.2-1549.73c8abc2 Throttler Version: 3.8.0.2-1549.73c8abc2 Object Image Version: 3.8.0.2-138636.7343cd5c2c3 -------------------- ECS Version: 3.8.0.2 -------------------- HW Gen : 2 HW Model: U-Series HW Code : S2600KP ------------------------- xDoctor Version: 4.8-98.0 -------------------------U uzlů Gen 1/2 odpovězte na formulář v e-mailu, že je potřeba pomoc. U uzlů 3. generace postupujte podle zbývající části tohoto článku znalostní databáze.
-
Zkontrolujte aktuální stav teplotních čidel. Níže vidíme "CRIT" na dvou uzlech, které indikují problémy na těchto dvou uzlech. Pokud se všechny uzly hlásí jako "OK", ale tato výstraha byla v poslední době přijata několikrát, může se jednat o opakující se problém. Pokud ano, odpovězte na formulář v e-mailu, že je nutná pomoc s opakovaným upozorněním na teplotu.
admin@node1:~> viprexec -i cs_hal sensors temp Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 53 Degrees Celsius Processor Temperature Temp OK 53 Degrees Celsius System Board Temperature Inlet Temp CRIT 40 Degrees Celsius; above critical threshold System Board Temperature Exhaust Temp OK 50 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 47 Degrees Celsius Processor Temperature Temp OK 49 Degrees Celsius System Board Temperature Inlet Temp CRIT 39 Degrees Celsius; above critical threshold System Board Temperature Exhaust Temp OK 50 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 46 Degrees Celsius Processor Temperature Temp OK 46 Degrees Celsius System Board Temperature Inlet Temp OK 35 Degrees Celsius System Board Temperature Exhaust Temp OK 47 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. ... ... ...
Pokud je více uzlů hlášeno jako "OK", může se jednat o problém v prostředí vašeho datového centra. Zkontrolujte, zda se v oblasti, kde se nachází systém ECS, nevyskytují žádné problémy, které by mohly zvyšovat teplotu systému ECS.
-
Zkontrolujte stav ventilátorů ECS.
admin@ecs:~>cs_hal sensors fan Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- System Board Fan Fan1 OK 12600 RPM System Board Fan Fan2 OK 12600 RPM System Board Fan Fan3 OK 16920 RPM System Board Fan Fan4 OK 16800 RPM System Board Fan Fan5 OK 17040 RPM System Board Fan Fan6 OK 16920 RPM System Board Fan Fan Redundancy OK fully redundant; NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
-
Odpovězte na formulář v e-mailu, že je potřeba pomoc, včetně výstupů teplotního čidla a výstupu ventilátoru.