ECS: Järjestelmä havaitsi solmussa korkean lämpötilan
Summary: Mitä voin tarkistaa, jos saan sähköpostihälytyksen, jossa ilmoitetaan, että järjestelmä on havainnut korkean lämpötilan anturin lukeman solmussa.
Instructions
-
Vahvista, mikä laitteisto ilmoituksen kohteena oleva solmu on.
admin@node1:~> sudo xdoctor -x Telegraf Version: 3.8.0.2-1549.73c8abc2 Fabric Version: 3.8.0.2-4347.d30cd09 Fabric-Zookeeper Version: 3.8.0.2-120.b4a1c5c Utilities Version: 3.7.0.4-1166.b78f3fe Influxdb Version: 3.8.0.2-1549.73c8abc2 Grafana Version: 3.8.0.2-1549.73c8abc2 Syslog Version: 3.8.0.2-4347.d30cd09 Service Version: 9.0.0.0-22840.479b013c74 Os Version: 3.8.0.2-2113.3fa664c.3 Fluxd Version: 3.8.0.2-1549.73c8abc2 Throttler Version: 3.8.0.2-1549.73c8abc2 Object Image Version: 3.8.0.2-138636.7343cd5c2c3 -------------------- ECS Version: 3.8.0.2 -------------------- HW Gen : 2 HW Model: U-Series HW Code : S2600KP ------------------------- xDoctor Version: 4.8-98.0 -------------------------Jos kyseessä on Gen 1/2 -solmu, vastaa sähköpostiviestissä olevaan lomakkeeseen, jossa ilmoitetaan avun tarpeesta. Jos kyseessä on Gen 3 -solmu, seuraa tämän tietämyskannan artikkelin loppuosaa.
-
Tarkista lämpötila-antureiden nykyinen tila. Alla näkyy CRIT kahdessa solmussa, mikä osoittaa ongelmia näissä kahdessa solmussa. Jos kaikki solmut ilmoittavat olevansa OK, mutta hälytys on vastaanotettu useita kertoja viime aikoina, kyseessä voi olla toistuva ongelma. Jos näin on, vastaa sähköpostiviestissä olevaan lomakkeeseen, jossa kerrotaan, että apua tarvitaan, toistuvalla lämpötilahälytyksellä.
admin@node1:~> viprexec -i cs_hal sensors temp Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 53 Degrees Celsius Processor Temperature Temp OK 53 Degrees Celsius System Board Temperature Inlet Temp CRIT 40 Degrees Celsius; above critical threshold System Board Temperature Exhaust Temp OK 50 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 47 Degrees Celsius Processor Temperature Temp OK 49 Degrees Celsius System Board Temperature Inlet Temp CRIT 39 Degrees Celsius; above critical threshold System Board Temperature Exhaust Temp OK 50 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 46 Degrees Celsius Processor Temperature Temp OK 46 Degrees Celsius System Board Temperature Inlet Temp OK 35 Degrees Celsius System Board Temperature Exhaust Temp OK 47 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. ... ... ...
Jos useat solmut eivät ole kunnossa, ongelma saattaa olla tietokeskuksen ympäristössä. Tarkista, että ECS:n sijaintialueella ei ole ongelmia, jotka saattaisivat nostaa ECS:n lämpötilaa.
-
Tarkista ECS-tuulettimien tila.
admin@ecs:~>cs_hal sensors fan Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- System Board Fan Fan1 OK 12600 RPM System Board Fan Fan2 OK 12600 RPM System Board Fan Fan3 OK 16920 RPM System Board Fan Fan4 OK 16800 RPM System Board Fan Fan5 OK 17040 RPM System Board Fan Fan6 OK 16920 RPM System Board Fan Fan Redundancy OK fully redundant; NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
-
Vastaa sähköpostissa olevaan lomakkeeseen, että apua tarvitaan, mukaan lukien sekä lämpötila-anturin että tuulettimen lähdöt.