ECS: Järjestelmä havaitsi solmussa korkean lämpötilan

Summary: Mitä voin tarkistaa, jos saan sähköpostihälytyksen, jossa ilmoitetaan, että järjestelmä on havainnut korkean lämpötilan anturin lukeman solmussa.

This article applies to This article does not apply to This article is not tied to any specific product. Not all product versions are identified in this article.

Instructions

  1. Vahvista, mikä laitteisto ilmoituksen kohteena oleva solmu on.

    admin@node1:~> sudo xdoctor -x
    Telegraf Version: 3.8.0.2-1549.73c8abc2
    Fabric Version: 3.8.0.2-4347.d30cd09
    Fabric-Zookeeper Version: 3.8.0.2-120.b4a1c5c
    Utilities Version: 3.7.0.4-1166.b78f3fe
    Influxdb Version: 3.8.0.2-1549.73c8abc2
    Grafana Version: 3.8.0.2-1549.73c8abc2
    Syslog Version: 3.8.0.2-4347.d30cd09
    Service Version: 9.0.0.0-22840.479b013c74
    Os Version: 3.8.0.2-2113.3fa664c.3
    Fluxd Version: 3.8.0.2-1549.73c8abc2
    Throttler Version: 3.8.0.2-1549.73c8abc2
    Object Image Version: 3.8.0.2-138636.7343cd5c2c3
    --------------------
    ECS Version: 3.8.0.2
    --------------------
    HW Gen  : 2
    HW Model: U-Series
    HW Code : S2600KP
    -------------------------
    xDoctor Version: 4.8-98.0
    -------------------------
    

    Jos kyseessä on Gen 1/2 -solmu, vastaa sähköpostiviestissä olevaan lomakkeeseen, jossa ilmoitetaan avun tarpeesta. Jos kyseessä on Gen 3 -solmu, seuraa tämän tietämyskannan artikkelin loppuosaa.

  2. Tarkista lämpötila-antureiden nykyinen tila. Alla näkyy CRIT kahdessa solmussa, mikä osoittaa ongelmia näissä kahdessa solmussa. Jos kaikki solmut ilmoittavat olevansa OK, mutta hälytys on vastaanotettu useita kertoja viime aikoina, kyseessä voi olla toistuva ongelma. Jos näin on, vastaa sähköpostiviestissä olevaan lomakkeeseen, jossa kerrotaan, että apua tarvitaan, toistuvalla lämpötilahälytyksellä.

    admin@node1:~> viprexec -i  cs_hal sensors temp
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    Processor         Temperature         Temp              OK      53 Degrees Celsius
    Processor         Temperature         Temp              OK      53 Degrees Celsius
    System Board      Temperature         Inlet Temp        CRIT    40 Degrees Celsius; above critical threshold
    System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    Processor         Temperature         Temp              OK      47 Degrees Celsius
    Processor         Temperature         Temp              OK      49 Degrees Celsius
    System Board      Temperature         Inlet Temp        CRIT    39 Degrees Celsius; above critical threshold
    System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    Processor         Temperature         Temp              OK      46 Degrees Celsius
    Processor         Temperature         Temp              OK      46 Degrees Celsius
    System Board      Temperature         Inlet Temp        OK      35 Degrees Celsius
    System Board      Temperature         Exhaust Temp      OK      47 Degrees Celsius
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
    
    ...
    ...
    ...

    Jos useat solmut eivät ole kunnossa, ongelma saattaa olla tietokeskuksen ympäristössä. Tarkista, että ECS:n sijaintialueella ei ole ongelmia, jotka saattaisivat nostaa ECS:n lämpötilaa.

  3. Tarkista ECS-tuulettimien tila.

    admin@ecs:~>cs_hal sensors fan
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    System Board      Fan                 Fan1              OK      12600 RPM
    System Board      Fan                 Fan2              OK      12600 RPM
    System Board      Fan                 Fan3              OK      16920 RPM
    System Board      Fan                 Fan4              OK      16800 RPM
    System Board      Fan                 Fan5              OK      17040 RPM
    System Board      Fan                 Fan6              OK      16920 RPM
    System Board      Fan                 Fan Redundancy    OK      fully redundant;
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
  4. Vastaa sähköpostissa olevaan lomakkeeseen, että apua tarvitaan, mukaan lukien sekä lämpötila-anturin että tuulettimen lähdöt.

 