ECS: Systemet oppdaget høy temperatur på en node
Summary: Hva kan jeg sjekke hvis jeg mottar et e-postvarsel som informerer meg om at systemet har oppdaget en høytemperatursensoravlesning på en node.
Instructions
-
Bekreft hvilken maskinvare den varslede noden er.
admin@node1:~> sudo xdoctor -x Telegraf Version: 3.8.0.2-1549.73c8abc2 Fabric Version: 3.8.0.2-4347.d30cd09 Fabric-Zookeeper Version: 3.8.0.2-120.b4a1c5c Utilities Version: 3.7.0.4-1166.b78f3fe Influxdb Version: 3.8.0.2-1549.73c8abc2 Grafana Version: 3.8.0.2-1549.73c8abc2 Syslog Version: 3.8.0.2-4347.d30cd09 Service Version: 9.0.0.0-22840.479b013c74 Os Version: 3.8.0.2-2113.3fa664c.3 Fluxd Version: 3.8.0.2-1549.73c8abc2 Throttler Version: 3.8.0.2-1549.73c8abc2 Object Image Version: 3.8.0.2-138636.7343cd5c2c3 -------------------- ECS Version: 3.8.0.2 -------------------- HW Gen : 2 HW Model: U-Series HW Code : S2600KP ------------------------- xDoctor Version: 4.8-98.0 -------------------------For 1/2 generasjons noder svarer du på skjemaet i e-posten om at hjelp er nødvendig. For 3. generasjons noder følger du resten av denne kunnskapsbaseartikkelen.
-
Kontroller gjeldende status for temperatursensorene. Nedenfor ser vi "CRIT" på to av nodene som indikerer problemer på disse to nodene. Hvis alle noder rapporterer som "OK", men dette varselet har blitt mottatt flere ganger nylig, kan det være et tilbakevendende problem. I så fall svarer du på skjemaet i e-posten om at det er behov for assistanse med et gjentakende temperaturvarsel.
admin@node1:~> viprexec -i cs_hal sensors temp Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 53 Degrees Celsius Processor Temperature Temp OK 53 Degrees Celsius System Board Temperature Inlet Temp CRIT 40 Degrees Celsius; above critical threshold System Board Temperature Exhaust Temp OK 50 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 47 Degrees Celsius Processor Temperature Temp OK 49 Degrees Celsius System Board Temperature Inlet Temp CRIT 39 Degrees Celsius; above critical threshold System Board Temperature Exhaust Temp OK 50 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 46 Degrees Celsius Processor Temperature Temp OK 46 Degrees Celsius System Board Temperature Inlet Temp OK 35 Degrees Celsius System Board Temperature Exhaust Temp OK 47 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. ... ... ...
Hvis flere noder rapporteres som ikke "OK", er det muligens et problem i miljøet til datasenteret ditt. Kontroller at det ikke er noen problemer i området der ECS er plassert som kan øke ECS-temperaturen.
-
Kontroller statusen til ECS-viftene.
admin@ecs:~>cs_hal sensors fan Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- System Board Fan Fan1 OK 12600 RPM System Board Fan Fan2 OK 12600 RPM System Board Fan Fan3 OK 16920 RPM System Board Fan Fan4 OK 16800 RPM System Board Fan Fan5 OK 17040 RPM System Board Fan Fan6 OK 16920 RPM System Board Fan Fan Redundancy OK fully redundant; NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
-
Svar på skjemaet i e-posten om at assistanse er nødvendig, inkludert både temperatursensorutgangene og vifteutgangene.