ECS: Systemet oppdaget høy temperatur på en node

Summary: Hva kan jeg sjekke hvis jeg mottar et e-postvarsel som informerer meg om at systemet har oppdaget en høytemperatursensoravlesning på en node.

This article applies to This article does not apply to This article is not tied to any specific product. Not all product versions are identified in this article.

Instructions

  1. Bekreft hvilken maskinvare den varslede noden er.

    admin@node1:~> sudo xdoctor -x
    Telegraf Version: 3.8.0.2-1549.73c8abc2
    Fabric Version: 3.8.0.2-4347.d30cd09
    Fabric-Zookeeper Version: 3.8.0.2-120.b4a1c5c
    Utilities Version: 3.7.0.4-1166.b78f3fe
    Influxdb Version: 3.8.0.2-1549.73c8abc2
    Grafana Version: 3.8.0.2-1549.73c8abc2
    Syslog Version: 3.8.0.2-4347.d30cd09
    Service Version: 9.0.0.0-22840.479b013c74
    Os Version: 3.8.0.2-2113.3fa664c.3
    Fluxd Version: 3.8.0.2-1549.73c8abc2
    Throttler Version: 3.8.0.2-1549.73c8abc2
    Object Image Version: 3.8.0.2-138636.7343cd5c2c3
    --------------------
    ECS Version: 3.8.0.2
    --------------------
    HW Gen  : 2
    HW Model: U-Series
    HW Code : S2600KP
    -------------------------
    xDoctor Version: 4.8-98.0
    -------------------------
    

    For 1/2 generasjons noder svarer du på skjemaet i e-posten om at hjelp er nødvendig. For 3. generasjons noder følger du resten av denne kunnskapsbaseartikkelen.

  2. Kontroller gjeldende status for temperatursensorene. Nedenfor ser vi "CRIT" på to av nodene som indikerer problemer på disse to nodene. Hvis alle noder rapporterer som "OK", men dette varselet har blitt mottatt flere ganger nylig, kan det være et tilbakevendende problem. I så fall svarer du på skjemaet i e-posten om at det er behov for assistanse med et gjentakende temperaturvarsel.

    admin@node1:~> viprexec -i  cs_hal sensors temp
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    Processor         Temperature         Temp              OK      53 Degrees Celsius
    Processor         Temperature         Temp              OK      53 Degrees Celsius
    System Board      Temperature         Inlet Temp        CRIT    40 Degrees Celsius; above critical threshold
    System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    Processor         Temperature         Temp              OK      47 Degrees Celsius
    Processor         Temperature         Temp              OK      49 Degrees Celsius
    System Board      Temperature         Inlet Temp        CRIT    39 Degrees Celsius; above critical threshold
    System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    Processor         Temperature         Temp              OK      46 Degrees Celsius
    Processor         Temperature         Temp              OK      46 Degrees Celsius
    System Board      Temperature         Inlet Temp        OK      35 Degrees Celsius
    System Board      Temperature         Exhaust Temp      OK      47 Degrees Celsius
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
    
    ...
    ...
    ...

    Hvis flere noder rapporteres som ikke "OK", er det muligens et problem i miljøet til datasenteret ditt. Kontroller at det ikke er noen problemer i området der ECS er plassert som kan øke ECS-temperaturen.

  3. Kontroller statusen til ECS-viftene.

    admin@ecs:~>cs_hal sensors fan
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    System Board      Fan                 Fan1              OK      12600 RPM
    System Board      Fan                 Fan2              OK      12600 RPM
    System Board      Fan                 Fan3              OK      16920 RPM
    System Board      Fan                 Fan4              OK      16800 RPM
    System Board      Fan                 Fan5              OK      17040 RPM
    System Board      Fan                 Fan6              OK      16920 RPM
    System Board      Fan                 Fan Redundancy    OK      fully redundant;
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
  4. Svar på skjemaet i e-posten om at assistanse er nødvendig, inkludert både temperatursensorutgangene og vifteutgangene.

 