ECS: System wykrył wysoką temperaturę węzła
Summary: Co mogę sprawdzić, jeśli otrzymam alert e-mail z informacją, że system wykrył odczyt czujnika wysokiej temperatury na węźle.
Instructions
-
Potwierdź, jakiego sprzętu dotyczy alert.
admin@node1:~> sudo xdoctor -x Telegraf Version: 3.8.0.2-1549.73c8abc2 Fabric Version: 3.8.0.2-4347.d30cd09 Fabric-Zookeeper Version: 3.8.0.2-120.b4a1c5c Utilities Version: 3.7.0.4-1166.b78f3fe Influxdb Version: 3.8.0.2-1549.73c8abc2 Grafana Version: 3.8.0.2-1549.73c8abc2 Syslog Version: 3.8.0.2-4347.d30cd09 Service Version: 9.0.0.0-22840.479b013c74 Os Version: 3.8.0.2-2113.3fa664c.3 Fluxd Version: 3.8.0.2-1549.73c8abc2 Throttler Version: 3.8.0.2-1549.73c8abc2 Object Image Version: 3.8.0.2-138636.7343cd5c2c3 -------------------- ECS Version: 3.8.0.2 -------------------- HW Gen : 2 HW Model: U-Series HW Code : S2600KP ------------------------- xDoctor Version: 4.8-98.0 -------------------------W przypadku węzłów Gen 1/2 odpowiedz na formularz w wiadomości e-mail, że wymagana jest pomoc. W przypadku węzłów Gen 3 postępuj zgodnie z pozostałą częścią tej bazy wiedzy.
-
Sprawdź aktualny stan czujników temperatury. Poniżej widzimy wartość "CRIT" na dwóch węzłach, wskazującą problemy na tych dwóch węzłach. Jeśli wszystkie węzły zgłaszają stan "OK", ale ten alert został ostatnio odebrany wiele razy, może to być powtarzający się problem. Jeśli tak, odpowiedz na formularz w wiadomości e-mail, że wymagana jest pomoc, z powtarzającym się alertem temperatury.
admin@node1:~> viprexec -i cs_hal sensors temp Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 53 Degrees Celsius Processor Temperature Temp OK 53 Degrees Celsius System Board Temperature Inlet Temp CRIT 40 Degrees Celsius; above critical threshold System Board Temperature Exhaust Temp OK 50 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 47 Degrees Celsius Processor Temperature Temp OK 49 Degrees Celsius System Board Temperature Inlet Temp CRIT 39 Degrees Celsius; above critical threshold System Board Temperature Exhaust Temp OK 50 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 46 Degrees Celsius Processor Temperature Temp OK 46 Degrees Celsius System Board Temperature Inlet Temp OK 35 Degrees Celsius System Board Temperature Exhaust Temp OK 47 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. ... ... ...
Jeśli wiele węzłów jest zgłaszanych jako nieprawidłowe, prawdopodobnie problem dotyczy środowiska centrum przetwarzania danych. Sprawdź, czy w obszarze, w którym znajduje się ECS, nie ma problemów, które mogą zwiększać temperaturę ECS.
-
Sprawdź stan wentylatorów ECS.
admin@ecs:~>cs_hal sensors fan Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- System Board Fan Fan1 OK 12600 RPM System Board Fan Fan2 OK 12600 RPM System Board Fan Fan3 OK 16920 RPM System Board Fan Fan4 OK 16800 RPM System Board Fan Fan5 OK 17040 RPM System Board Fan Fan6 OK 16920 RPM System Board Fan Fan Redundancy OK fully redundant; NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
-
Odpowiedz na formularz w wiadomości e-mail, że wymagana jest pomoc, w tym zarówno wyjścia czujnika temperatury, jak i wyjścia wentylatora.