ECS: O sistema detectou alta temperatura em um nó
Summary: O que posso verificar se receber um alerta por e-mail informando que o sistema detectou uma leitura de sensor de alta temperatura em um nó.
Instructions
-
Confirme qual é o hardware do nó alertado.
admin@node1:~> sudo xdoctor -x Telegraf Version: 3.8.0.2-1549.73c8abc2 Fabric Version: 3.8.0.2-4347.d30cd09 Fabric-Zookeeper Version: 3.8.0.2-120.b4a1c5c Utilities Version: 3.7.0.4-1166.b78f3fe Influxdb Version: 3.8.0.2-1549.73c8abc2 Grafana Version: 3.8.0.2-1549.73c8abc2 Syslog Version: 3.8.0.2-4347.d30cd09 Service Version: 9.0.0.0-22840.479b013c74 Os Version: 3.8.0.2-2113.3fa664c.3 Fluxd Version: 3.8.0.2-1549.73c8abc2 Throttler Version: 3.8.0.2-1549.73c8abc2 Object Image Version: 3.8.0.2-138636.7343cd5c2c3 -------------------- ECS Version: 3.8.0.2 -------------------- HW Gen : 2 HW Model: U-Series HW Code : S2600KP ------------------------- xDoctor Version: 4.8-98.0 -------------------------Para os nós de 1ª/2ª geração, responda ao formulário no e-mail em que a assistência é necessária. Para nós de 3ª geração, siga o restante deste artigo da KB.
-
Verifique o status atual dos sensores de temperatura. Abaixo, vemos "CRIT" em dois dos nós indicando problemas nesses dois nós. Se todos os nós relatarem como OK, mas esse alerta tiver recebido esse alerta várias vezes recentemente, poderá ser um problema recorrente. Em caso afirmativo, responda ao formulário no e-mail que a assistência é necessária com um alerta de temperatura recorrente.
admin@node1:~> viprexec -i cs_hal sensors temp Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 53 Degrees Celsius Processor Temperature Temp OK 53 Degrees Celsius System Board Temperature Inlet Temp CRIT 40 Degrees Celsius; above critical threshold System Board Temperature Exhaust Temp OK 50 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 47 Degrees Celsius Processor Temperature Temp OK 49 Degrees Celsius System Board Temperature Inlet Temp CRIT 39 Degrees Celsius; above critical threshold System Board Temperature Exhaust Temp OK 50 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 46 Degrees Celsius Processor Temperature Temp OK 46 Degrees Celsius System Board Temperature Inlet Temp OK 35 Degrees Celsius System Board Temperature Exhaust Temp OK 47 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. ... ... ...
Se vários nós não estiverem "OK", possivelmente será um problema no ambiente do seu data center. Verifique se não há problemas na área em que o ECS está localizado que possam estar aumentando a temperatura do ECS.
-
Verifique o status dos ventiladores do ECS.
admin@ecs:~>cs_hal sensors fan Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- System Board Fan Fan1 OK 12600 RPM System Board Fan Fan2 OK 12600 RPM System Board Fan Fan3 OK 16920 RPM System Board Fan Fan4 OK 16800 RPM System Board Fan Fan5 OK 17040 RPM System Board Fan Fan6 OK 16920 RPM System Board Fan Fan Redundancy OK fully redundant; NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
-
Responda ao formulário no e-mail que a assistência é necessária, incluindo as saídas do sensor de temperatura e do ventilador.