ECS: O sistema detectou alta temperatura em um nó

Summary: O que posso verificar se receber um alerta por e-mail informando que o sistema detectou uma leitura de sensor de alta temperatura em um nó.

This article applies to This article does not apply to This article is not tied to any specific product. Not all product versions are identified in this article.

Instructions

  1. Confirme qual é o hardware do nó alertado.

    admin@node1:~> sudo xdoctor -x
    Telegraf Version: 3.8.0.2-1549.73c8abc2
    Fabric Version: 3.8.0.2-4347.d30cd09
    Fabric-Zookeeper Version: 3.8.0.2-120.b4a1c5c
    Utilities Version: 3.7.0.4-1166.b78f3fe
    Influxdb Version: 3.8.0.2-1549.73c8abc2
    Grafana Version: 3.8.0.2-1549.73c8abc2
    Syslog Version: 3.8.0.2-4347.d30cd09
    Service Version: 9.0.0.0-22840.479b013c74
    Os Version: 3.8.0.2-2113.3fa664c.3
    Fluxd Version: 3.8.0.2-1549.73c8abc2
    Throttler Version: 3.8.0.2-1549.73c8abc2
    Object Image Version: 3.8.0.2-138636.7343cd5c2c3
    --------------------
    ECS Version: 3.8.0.2
    --------------------
    HW Gen  : 2
    HW Model: U-Series
    HW Code : S2600KP
    -------------------------
    xDoctor Version: 4.8-98.0
    -------------------------
    

    Para os nós de 1ª/2ª geração, responda ao formulário no e-mail em que a assistência é necessária. Para nós de 3ª geração, siga o restante deste artigo da KB.

  2. Verifique o status atual dos sensores de temperatura. Abaixo, vemos "CRIT" em dois dos nós indicando problemas nesses dois nós. Se todos os nós relatarem como OK, mas esse alerta tiver recebido esse alerta várias vezes recentemente, poderá ser um problema recorrente. Em caso afirmativo, responda ao formulário no e-mail que a assistência é necessária com um alerta de temperatura recorrente.

    admin@node1:~> viprexec -i  cs_hal sensors temp
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    Processor         Temperature         Temp              OK      53 Degrees Celsius
    Processor         Temperature         Temp              OK      53 Degrees Celsius
    System Board      Temperature         Inlet Temp        CRIT    40 Degrees Celsius; above critical threshold
    System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    Processor         Temperature         Temp              OK      47 Degrees Celsius
    Processor         Temperature         Temp              OK      49 Degrees Celsius
    System Board      Temperature         Inlet Temp        CRIT    39 Degrees Celsius; above critical threshold
    System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    Processor         Temperature         Temp              OK      46 Degrees Celsius
    Processor         Temperature         Temp              OK      46 Degrees Celsius
    System Board      Temperature         Inlet Temp        OK      35 Degrees Celsius
    System Board      Temperature         Exhaust Temp      OK      47 Degrees Celsius
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
    
    ...
    ...
    ...

    Se vários nós não estiverem "OK", possivelmente será um problema no ambiente do seu data center. Verifique se não há problemas na área em que o ECS está localizado que possam estar aumentando a temperatura do ECS.

  3. Verifique o status dos ventiladores do ECS.

    admin@ecs:~>cs_hal sensors fan
    
    Output from host : xxx.xxx.xxx.xxx
    Entity            Type                Label             Status  Info
    -----             -----               -----             -----   -----
    System Board      Fan                 Fan1              OK      12600 RPM
    System Board      Fan                 Fan2              OK      12600 RPM
    System Board      Fan                 Fan3              OK      16920 RPM
    System Board      Fan                 Fan4              OK      16800 RPM
    System Board      Fan                 Fan5              OK      17040 RPM
    System Board      Fan                 Fan6              OK      16920 RPM
    System Board      Fan                 Fan Redundancy    OK      fully redundant;
    
    NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
  4. Responda ao formulário no e-mail que a assistência é necessária, incluindo as saídas do sensor de temperatura e do ventilador.

 

Affected Products

ECS
Article Properties
Article Number: 000227188
Article Type: How To
Last Modified: 30 Jul 2024
Version:  2