ECS: Systemet har upptäckt hög temperatur på en nod
Summary: Vad kan jag kontrollera om jag får ett e-postmeddelande som informerar mig om att systemet har detekterat en avläsning av en högtemperatursensor på en nod.
Instructions
-
Bekräfta vilken maskinvara den avvarnade noden är.
admin@node1:~> sudo xdoctor -x Telegraf Version: 3.8.0.2-1549.73c8abc2 Fabric Version: 3.8.0.2-4347.d30cd09 Fabric-Zookeeper Version: 3.8.0.2-120.b4a1c5c Utilities Version: 3.7.0.4-1166.b78f3fe Influxdb Version: 3.8.0.2-1549.73c8abc2 Grafana Version: 3.8.0.2-1549.73c8abc2 Syslog Version: 3.8.0.2-4347.d30cd09 Service Version: 9.0.0.0-22840.479b013c74 Os Version: 3.8.0.2-2113.3fa664c.3 Fluxd Version: 3.8.0.2-1549.73c8abc2 Throttler Version: 3.8.0.2-1549.73c8abc2 Object Image Version: 3.8.0.2-138636.7343cd5c2c3 -------------------- ECS Version: 3.8.0.2 -------------------- HW Gen : 2 HW Model: U-Series HW Code : S2600KP ------------------------- xDoctor Version: 4.8-98.0 -------------------------För Gen 1/2-noder svarar du på formuläret i e-postmeddelandet om att hjälp krävs. För Gen 3-noder följer du resten av den här kunskapsbasen.
-
Kontrollera temperatursensorernas aktuella status. Nedan ser vi "CRIT" på två av noderna som indikerar problem på dessa två noder. Om alla noder rapporterar som "OK" men den här aviseringen har fått den här aviseringen flera gånger nyligen kan det vara ett återkommande problem. Svara i så fall på formuläret i mejlet om att hjälp krävs med en återkommande temperaturvarning.
admin@node1:~> viprexec -i cs_hal sensors temp Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 53 Degrees Celsius Processor Temperature Temp OK 53 Degrees Celsius System Board Temperature Inlet Temp CRIT 40 Degrees Celsius; above critical threshold System Board Temperature Exhaust Temp OK 50 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 47 Degrees Celsius Processor Temperature Temp OK 49 Degrees Celsius System Board Temperature Inlet Temp CRIT 39 Degrees Celsius; above critical threshold System Board Temperature Exhaust Temp OK 50 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- Processor Temperature Temp OK 46 Degrees Celsius Processor Temperature Temp OK 46 Degrees Celsius System Board Temperature Inlet Temp OK 35 Degrees Celsius System Board Temperature Exhaust Temp OK 47 Degrees Celsius NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information. ... ... ...
Om flera noder rapporteras som "OK" kan det bero på ett problem i datacentrets miljö. Kontrollera att det inte finns några problem i det område där ECS finns som kan öka ECS-temperaturen.
-
Kontrollera status för ECS-fläktarna.
admin@ecs:~>cs_hal sensors fan Output from host : xxx.xxx.xxx.xxx Entity Type Label Status Info ----- ----- ----- ----- ----- System Board Fan Fan1 OK 12600 RPM System Board Fan Fan2 OK 12600 RPM System Board Fan Fan3 OK 16920 RPM System Board Fan Fan4 OK 16800 RPM System Board Fan Fan5 OK 17040 RPM System Board Fan Fan6 OK 16920 RPM System Board Fan Fan Redundancy OK fully redundant; NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
-
Svara på formuläret i e-postmeddelandet om att hjälp krävs, inklusive både temperatursensorutgångar och fläktutgångar.