Default Power Configurations With Extended Power Performance (EPP)

Default Power Configurations on the Chassis when EPP mode is enabled or disabled:
  • On 3000W AC six PSUs configuration with Grid Redundancy policy:

    EPP Enabled – DPSE Disabled, SPOPR Disabled, MPCM Disabled, SBPM Disabled

  • Running the command racadm racresetcfg on 3000W AC PSU configuration, resets the power configurations to the following values:

    EPP Disabled – DPSE Disabled, SPOPR Disabled, MPCM Disabled, SBPM Disabled

  • On 3000W AC with less than six PSUs configuration:

    EPP Disabled – DPSE Disabled, SPOPR Disabled, MPCM Disabled, SBPM Disabled

  • On 2700W AC PSU configuration:

    EPP Disabled – DPSE Disabled, SPOPR Enabled, MPCM Disabled, SBPM Disabled

  • Using racadm racresetcfg on 2700W AC PSU configuration, resets the power configurations to the following values:

    EPP Disabled – DPSE Disabled, SPOPR Disabled, MPCM Disabled, SBPM Disabled

  • On a Fresh Air enabled chassis configurations, 3000W PSUs are displayed as 2800W and EPP is not supported.