Dell PowerEdge T630 Owner's Manual

Wiring instructions for a DC power supply unit

Your system supports up to two –(48–60) V DC power supply units (when available).

Input requirements

NOTE: For equipment using –(48–60) V DC power supply units (PSUs), a qualified electrician must perform all connections to DC power and to safety grounds. Do not attempt connecting to DC power or installing grounds yourself. All electrical wiring must comply with applicable local or national codes and practices. Damage due to servicing that is not authorized by Dell is not covered by your warranty. Read and follow all safety instructions that came with the product.
CAUTION: Wire the unit with copper only, unless otherwise specified, use only 10 American Wire Gauge (AWG) wire rated minimum 90 ºC for source and return. Protect the –(48–60) V DC (1 wire) with a branch circuit over-current protection rated 50 A for DC with a high interrupt current rating.
CAUTION: Connect the equipment to a –(48–60) V DC supply source that is electrically isolated from the AC source (reliably grounded –(48–60) V DC SELV source). Ensure that the –(48–60) V DC source is efficiently secured to earth (ground).
NOTE: A readily accessible disconnect device that is approved and rated, is incorporated in the field wiring.
  • Supply voltage: –(48–60) V DC
  • Current consumption: 32 A (maximum)

Kit contents

  • Dell part number 6RYJ9 terminal block or equivalent (1)
  • #6-32 nut equipped with lock washer (1)

Required tools

Wire-stripper pliers, capable of removing insulation from size 10 AWG solid or stranded, insulated copper wire.

NOTE: Use alpha wire part number 3080 or equivalent (65/30 stranding).

Required wires

  • One UL 10 AWG, 2 m maximum (stranded) black wire [–(48–60) V DC]
  • One UL 10 AWG, 2 m maximum (stranded) red wire (V DC return)
  • One UL 10 AWG, 2 m maximum green/yellow, green with a yellow stripe, stranded wire (safety ground)

Évaluez ce contenu

Précis
Utile
Facile à comprendre
Avez-vous trouvé cet article utile ?
0/3000 characters
  Veuillez attribuer une note (1 à 5 étoiles).
  Veuillez attribuer une note (1 à 5 étoiles).
  Veuillez attribuer une note (1 à 5 étoiles).
  Veuillez indiquer si l’article a été utile ou non.
  Les commentaires ne doivent pas contenir les caractères spéciaux : <>()\