Dell PowerEdge FX2 and FX2s Enclosure Owner's Manual

Installing the power interposer board

Prerequisites

CAUTION: Many repairs may only be done by a certified service technician. You should only perform troubleshooting and simple repairs as authorized in your product documentation, or as directed by the online or telephone service and support team. Damage due to servicing that is not authorized by Dell is not covered by your warranty. Read and follow the safety instructions that came with the product.
NOTE: This is a field replaceable unit (FRU). Removal and installation procedures should be performed only by Dell certified service technicians.
  1. Ensure that you read the Safety instructions.
  2. Follow the procedure listed in Before working inside your system.
  3. Remove the power interposer board.
    NOTE: You must remove the power interposer board to replace a faulty power interposer board.

Steps

  1. Place the power interposer board in the carrier.
  2. Install the four screws to secure the power interposer board to the carrier.
  3. Reconnect the power bus bar and cable cover to the power interposer board.
  4. Reconnect the power bus bar and cable cover to the midplane assembly.
  5. Install the Mylar insulator.

Next steps

  1. Install the midplane assembly.
  2. Follow the procedure listed in After working inside your system.

Ohodnotiť tento obsah

Presné
Užitočné
Jednoducho pochopiteľné
Bol pre vás tento článok užitočný?
0/3000 characters
  Vyberte, prosím, hodnotenie (1 až 5 hviezdičiek).
  Vyberte, prosím, hodnotenie (1 až 5 hviezdičiek).
  Vyberte, prosím, hodnotenie (1 až 5 hviezdičiek).
  Vyberte, prosím, či vám článok pomohol alebo nie.
  Poznámky nemôžu obsahovať nasledujúce špeciálne znaky: <>()\