Data Domain: NVRAM Remote Battery Failure Alert | NVRAM-00202

概要: This article explains the cause and resolution of the NVRAMRemoteBatteryFailure alert (Event ID: EVT-NVRAM-00202) on Data Domain systems; This alert indicates a critical hardware fault with the NVRAM remote battery, which must be resolved before the file system can be accessed. ...

この記事は次に適用されます: この記事は次には適用されません: この記事は、特定の製品に関連付けられていません。 すべての製品パージョンがこの記事に記載されているわけではありません。

現象

  • Event ID: EVT-NVRAM-00202
    • Alert: NVRAMRemoteBatteryFailure
    • Message: "A hardware fault was detected with an NVRAM remote battery and it may need to be replaced."
  • Filesystem is down with NVRAM alerts posted.

Example:

  • Alert ID:          EVT-NVRAM-00202
    Severity:         Critical
    Class:             hardwareFailure
    Object:            Slot=%s
    Info:                Cause=%s (see list below)
    
    Message:         A hardware fault was detected with an NVRAM remote battery and it may need to be replaced
    
    Description:     The remote battery for an NVRAM card is not in an usable state. The file system cannot be accessed until the fault is corrected or the NVRAM remote battery is replaced.

APPLIES TO

  • All Data Domain systems

原因

This alert is triggered when the system detects that the NVRAM remote battery is unreliable or unusable. The specific cause is detailed in the alert message (Info: Cause=). Possible causes include:

  • Unable to retrieve NVRAM battery status
  • Battery not detected
  • Battery not charging
  • Voltage levels critically high:
    • Battery 1 voltage: High Critical
    • Battery 2 voltage: High Critical
    • Battery 3 voltage: High Critical
  • Multiple battery failures detected

解決方法

      To resolve the issue:

      1. Check iDRAC (System Event Log) - SDPM/VOSS systems only 
      2. Inspect physical connections:

        • Ensure all cables between the NVRAM card, and the remote battery are securely connected.
        • Verify that the power cable from the system to the remote battery unit is properly seated.
        • If the system was previously powered off for an extended period of time, wait for the batteries to charge >=80%
      3. Replace faulty components:

        • If any cables are damaged or defective, replace them.
        • If all connections are intact and the alert persists, replace the remote backup battery unit.

      対象製品

      PowerProtect Data Manager Appliance, Data Domain, PowerProtect Data Manager
      文書のプロパティ
      文書番号: 000042368
      文書の種類: Solution
      最終更新: 25 8月 2026
      バージョン:  7
      質問に対する他のDellユーザーからの回答を見つける
      サポート サービス
      お使いのデバイスがサポート サービスの対象かどうかを確認してください。