Processor
Processor type One or two Intel Xeon processor E5-2400 and E5-2400 v2 product family
Expansion Bus  
Bus type PCI Express Generation 2 and Generation 3
Expansion slots using riser card for a one processor system:  
  Riser 1 (Slot 1) One half-height, half-length x4 link with x8 slot
  Riser 2 (Slot 2) One full-height, full-length x8 link with x16 slot
(Slot 3) One full-height, half-length x4 link with x8 slot
(Slot 4) One full-height, half-length x4 link with x8 slot
Expansion slots using riser card for a two processor system:  
  Riser 1 (Slot 1) One half-height, half-length x16 link with x16 slot
  Riser 2 (Slot 2) One full-height, full-length x8 link with x16 slot
(Slot 3) One full-height, half-length x8 link with x16 slot
(Slot 4) One full-height, half-length x8 link with x16 slot
  • NOTE: If you install a second processor, you must:
    • remove the dummy fan from the FAN6 slot
    • install a cooling fan in the FAN6 slot
    • upgrade both the expansion-card risers (riser 1 and riser 2)
Memory  
Architecture 1600 MT/s, 1333 MT/s, or 1066 MT/s DDR3 and LV-DDR3 DIMMs
Memory module sockets Twelve 240-pin
Memory module capacities  
  RDIMMs 2 GB (single-rank), 4 GB (single- and dual-rank), 8 GB (dual-rank), 16 GB (dual-rank), and 32 GB (quad-rank)
  UDIMMs 2 GB (single-rank) and 4 GB (dual-rank)
Minimum RAM 2 GB (single processor configuration)
Maximum RAM 384 GB
Drives  
Hard drives

Up to eight 3.5 inch or 2.5 inch, internal, hot-swappable SAS, SATA, SAS SSD. SATA SSD, or Nearline SAS hard drives in hard-drive slots 0 through 7.

Up to four 3.5 inch or 2.5 inch, internal, hot-swappable SAS, SATA, SAS SSD, SATA SSD, or Nearline SAS hard drives in hard-drive slots 0 through 3 for a software RAID system.

Optical drive One optional slimline SATA DVD-ROM or DVD+/-RW drive
  • NOTE: DVD devices are data only.
Connectors  
Back  
  NIC Two RJ-45 10/100/1000 Mbps
  Serial 9-pin, DTE, 16550-compatible
  USB Two 4-pin, USB 2.0-compliant
  Video 15-pin VGA
  iDRAC7 (Optional) One 1GbE Ethernet port
  External vFlash card (Optional) vFlash memory card
  • NOTE: The card slot is available for use only if the iDRAC7 Enterprise license is installed on your system.
Front  
  USB Two 4-pin, USB 2.0-compliant
  Video 15-pin VGA
Internal  
  USB One 4-pin, USB 2.0-compliant
  Internal Dual SD Module (IDSDM) Two optional flash memory card slots with the internal SD module
  • NOTE: One card slot is dedicated for redundancy.
Video  
Video type Integrated Matrox G200
Video memory 16 MB shared
   
Expanded Operating Temperature  
  • NOTE: When operating in the expanded temperature range, system performance may be impacted.
  • NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD and in the System Event Log.
  < 10% of annual operating hours 5 °C to 40 °C at 5% to 85% RH with 26 °C dew point.
  • NOTE: Outside the standard operating temperature (10 °C to 35 °C), the system can operate down to 5 °C or up to 40 °C for a maximum of 10% of its annual operating hours.

For temperatures between 35 °C and 40 °C, de-rate maximum allowable dry bulb temperature by 1 °C per 175 m above 950 m (1 °F per 319 ft).

  < 1% of annual operating hours –5 °C to 45 °C at 5% to 90% RH with 26 °C dew point.
  • NOTE: Outside the standard operating temperature (10 °C to 35 °C), the system can operate down to –5 °C or up to 45 °C for a maximum of 1% of its annual operating hours.

For temperatures between 40 °C and 45 °C, de-rate maximum allowable dry bulb temperature by 1 °C per 125 m above 950 m (1 °F per 228 ft).

  Expanded Operating Temperature Restrictions
  • Do not perform a cold startup below 5 °C.
  • Allow processor performance degrade.
  • Non-redundant power supplies are not supported.
  • Non Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.
  • Maximum altitude for the operating temperature must be 3050 m (10,000 ft).
Environmental  
  • NOTE: For additional information about environmental measurements for specific system configurations, see dell.com/environmental_datasheets.
Temperature  
  Maximum Temperature Gradient (Operating and Storage) 20 °C/h (36 °F/h)
  Storage Temperature Limits –40 °C to 65 °C (–40 °F to 149 °F)
Temperature (Continuous Operation)
  Temperature Ranges (for altitude less than 950 m or 3117 ft) 10 °C to 35 °C (50 °F to 95 °F) with no direct sunlight on the equipment.
  Humidity Percentage Range 10% to 80% Relative Humidity with 26 °C (78.8 °F) maximum dew point.
Relative Humidity  
  Storage 5% to 95% RH with 33 °C (91 °F) maximum dew point. Atmosphere must be non-condensing at all times.
Maximum Vibration  
  Operating 0.26 G rms at 5 Hz to 350 Hz (all operation orientations).
  Storage 1.87 G rms at 10 Hz to 500 Hz for 15 min (all six sides tested).
Maximum Shock  
  Operating One shock pulse in the positive z axis of 31 G for 2.6 ms in all operational orientations.
  Storage Six consecutively executed shock pulses in the positive and negative x, y, and z axes (one pulse on each side of the system) of 71 G for up to 2 ms.
Maximum Altitude  
  Operating

3048 m ( 10,000 ft).

  Storage 12,000 m (39,370 ft).
Operating Altitude De-rating
  Up to 35 °C (95 °F) Maximum temperature is reduced by 1 °C/300 m (1 °F/547 ft) above 950 m (3,117 ft).
  35 °C to 40 °C (95 °F to 104 °F) Maximum temperature is reduced by 1 °C/175 m (1 °F/319 ft) above 950 m (3,117 ft).
  40 °C to 45 °C (104 °F to 113 °F) Maximum temperature is reduced by 1 °C/125 m (1 °F/228 ft) above 950 m (3,117 ft).
Particulate Contamination
  • NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the responsibility of the customer.
  Air Filtration
  • NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
  • NOTE: Air entering the data center must have MERV11 or MERV13 filtration.
  Conductive Dust
  • NOTE: Applies to data center and non-data center environments.
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
  Corrosive Dust
  • NOTE: Applies to data center and non-data center environments.
  • Air must be free of corrosive dust.
  • Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
Gaseous Contamination
  • NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
  Copper Coupon Corrosion Rate <300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
  Silver Coupon Corrosion Rate <200 Å/month as defined by AHSRAE TC9.9.

Rate this content

Accurate
Useful
Easy to understand
Was this article helpful?
0/3000 characters
  Please provide ratings (1-5 stars).
  Please provide ratings (1-5 stars).
  Please provide ratings (1-5 stars).
  Please select whether the article was helpful or not.
  Comments cannot contain these special characters: <>()\