Dell PowerEdge R750 Installation and Service Manual

Wiring instructions for a DC power supply unit

Your system supports up to two –(48–60) V DC power supply units (PSUs).

Input requirements

NOTE:对于使用 -(48-60) V DC 电源装置 (PSU) 的设备,必须由合格的电工执行与 DC 电源连接相关的所有工作并安全接地。请不要尝试亲自连接至直流电源或安装地线。所有电气布线必须遵从适用的当地或国家/地区规范和惯例。任何未经 Dell 授权的服务所导致的损坏均不在保修范围之列。请阅读并遵循产品附带的所有安全说明。
CAUTION:Wire the unit with copper only, unless otherwise specified, use only 10 American Wire Gauge (AWG) wire rated minimum 90ºC for source and return. Protect the –(48–60) V DC (1 wire) with a branch circuit over-current protection rated 50 A for DC with a high interrupt current rating.
CAUTION:Connect the equipment to a –(48–60) V DC supply source that is electrically isolated from the AC source (reliably grounded –(48–60) V DC SELV source). Ensure that the –(48–60) V DC source is efficiently secured to earth (ground).
NOTE:A readily accessible disconnect device that is suitably approved and rated shall be incorporated in the field wiring.
  • Supply voltage: –(48–60) V DC
  • Current consumption: 32 A (maximum)

Kit contents

  • Dell part number 6RYJ9 terminal block or equivalent (1)
  • #6-32 nut equipped with lock washer (1)

Required tools

Wire-stripper pliers capable of removing insulation from size 10 AWG solid or stranded, insulated copper wire.

NOTE:Use alpha wire part number 3080 or equivalent (65/30 stranding).

Required wires

  • One UL 10 AWG, 2 m maximum (stranded) black wire [–(48–60) V DC].
  • One UL 10 AWG, 2 m maximum (stranded) red wire (V DC return).
  • One UL 10 AWG, 2 m maximum, green with a yellow stripe, stranded wire (safety ground).