Wiring instructions
for a DC power supply unit
Your system supports up to two –(48–60) V DC
power supply units (PSUs).
Input requirements
NOTE:对于使用 -(48-60) V DC 电源装置 (PSU) 的设备,必须由合格的电工执行与 DC 电源连接相关的所有工作并安全接地。请不要尝试亲自连接至直流电源或安装地线。所有电气布线必须遵从适用的当地或国家/地区规范和惯例。任何未经 Dell 授权的服务所导致的损坏均不在保修范围之列。请阅读并遵循产品附带的所有安全说明。
CAUTION:Wire
the unit with copper only, unless otherwise specified, use only 10
American Wire Gauge (AWG) wire rated minimum 90ºC for source and return.
Protect the –(48–60) V DC (1 wire) with a branch circuit over-current
protection rated 50 A for DC with a high interrupt current rating.
CAUTION:Connect the equipment to a –(48–60) V DC supply source
that is electrically isolated from the AC source (reliably grounded
–(48–60) V DC SELV source). Ensure that the –(48–60) V DC source is
efficiently secured to earth (ground).
NOTE:A readily accessible
disconnect device that is suitably approved and rated shall be incorporated
in the field wiring.
- Supply voltage:
–(48–60) V DC
- Current
consumption: 32 A (maximum)
Kit contents
- Dell part
number 6RYJ9 terminal block or equivalent (1)
- #6-32 nut
equipped with lock washer (1)
Required tools
Wire-stripper pliers capable of removing insulation
from size 10 AWG solid or stranded, insulated copper wire.
NOTE:Use alpha wire part
number 3080 or equivalent (65/30 stranding).
Required wires
- One UL 10
AWG, 2 m maximum (stranded) black wire [–(48–60) V DC].
- One UL 10
AWG, 2 m maximum (stranded) red wire (V DC return).
- One UL 10
AWG, 2 m maximum, green with a yellow stripe, stranded wire (safety
ground).