ECS: RAP015: Temperature Failure; Symptom Code: 2010

Summary: A temperature sensor on the node is reporting at a critical level has been reached.

This article applies to This article does not apply to This article is not tied to any specific product. Not all product versions are identified in this article.

Symptoms

A temperature sensor has detected a temperature that is above a critical threshold.
A component may not be operating correctly that is causing a temperature sensor to report that a critical level has been reached.
A temperature sensor on the node is reporting that a critical level has been reached.

Cause

An issue has occurred that caused a temperature sensor to go above a critical level.

Resolution

For Gen2, scroll to the bottom.

Gen3 Hardware: 

1. Check the status of the temperature sensors using cs_hal on the reported node.

Command: 
#cs_hal sensors temp
 
Example: For Gen3, there are only three Temp sensors as follows.
 
admin@n1-mgmt:~>  cs_hal sensors temp
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      53 Degrees Celsius
Processor         Temperature         Temp              OK      54 Degrees Celsius
System Board      Temperature         Inlet Temp        CRIT    40 Degrees Celsius; above critical threshold
System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
admin@n1-mgmt:~>
2.Check all nodes in the rack and see if other nodes are reporting temp sensor not "OK"

Command: 
viprexec -i  cs_hal sensors temp

Example: In this example, multiple nodes in the upper half of the rack are reporting inlet temp too high. 
admin@n1-mgmt:~> viprexec -i  cs_hal sensors temp

Output from host : 192.168.219.1
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      53 Degrees Celsius
Processor         Temperature         Temp              OK      53 Degrees Celsius
System Board      Temperature         Inlet Temp        CRIT    40 Degrees Celsius; above critical threshold
System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.2
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      47 Degrees Celsius
Processor         Temperature         Temp              OK      49 Degrees Celsius
System Board      Temperature         Inlet Temp        CRIT    39 Degrees Celsius; above critical threshold
System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.3
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      46 Degrees Celsius
Processor         Temperature         Temp              OK      46 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      35 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      47 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.4
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      48 Degrees Celsius
Processor         Temperature         Temp              OK      50 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      35 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      47 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.5
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      48 Degrees Celsius
Processor         Temperature         Temp              OK      50 Degrees Celsius
System Board      Temperature         Inlet Temp        WARN    38 Degrees Celsius; above non-critical threshold
System Board      Temperature         Exhaust Temp      OK      49 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.6
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      50 Degrees Celsius
Processor         Temperature         Temp              OK      52 Degrees Celsius
System Board      Temperature         Inlet Temp        CRIT    39 Degrees Celsius; above critical threshold
System Board      Temperature         Exhaust Temp      OK      51 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.7
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      45 Degrees Celsius
Processor         Temperature         Temp              OK      48 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      36 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      47 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.8
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      51 Degrees Celsius
Processor         Temperature         Temp              OK      49 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      31 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      43 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.9
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      52 Degrees Celsius
Processor         Temperature         Temp              OK      51 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      30 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      42 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.10
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      54 Degrees Celsius
Processor         Temperature         Temp              OK      51 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      28 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      41 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
 192.168.219.7
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      45 Degrees Celsius
Processor         Temperature         Temp              OK      48 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      36 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      47 Degrees Celsius

Output from host : 192.168.219.11
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      56 Degrees Celsius
Processor         Temperature         Temp              OK      55 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      27 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      40 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.12
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      59 Degrees Celsius
Processor         Temperature         Temp              OK      59 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      26 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      38 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.13
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      51 Degrees Celsius
Processor         Temperature         Temp              OK      49 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      26 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      36 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.14
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      57 Degrees Celsius
Processor         Temperature         Temp              OK      60 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      26 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      38 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.15
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      59 Degrees Celsius
Processor         Temperature         Temp              OK      59 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      26 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      39 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.16
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      56 Degrees Celsius
Processor         Temperature         Temp              OK      56 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      26 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      38 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
admin@n1-mgmt:~>

3. Possible Scenarios:
  1. One node only reporting a sensor or more: If the issue is seen on only one node where temperature is reporting not "OK," then this mostly likely indicates a part issue or the node not having good airflow due to more likely an internal issue than a rack issue.
  2. Multiple nodes are affected this more an environmental issue within the rack itself or possible the Data center


4. Check fans are running OK. If not then a fan may be need replacement.

Command:

#cs_hal sensors fan
Example: 
admin@ecs:~>cs_hal sensors fan

Output from host : 192.168.219.1
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
System Board      Fan                 Fan1              OK      12600 RPM
System Board      Fan                 Fan2              OK      12600 RPM
System Board      Fan                 Fan3              OK      16920 RPM
System Board      Fan                 Fan4              OK      16800 RPM
System Board      Fan                 Fan5              OK      17040 RPM
System Board      Fan                 Fan6              OK      16920 RPM
System Board      Fan                 Fan Redundancy    OK      fully redundant;

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
3. If all fans are reporting OK, this means that there is no issues with the fan systems. Engage the Power Edge team to check if a part needs replacement. If any fans are reporting issue then follow ECS: Dial Home: Fan Failure; SymptomCode: 2008

4. Important : Use https://central.dell.com/case-lookup/  and lookup the PSNT (Product Serial Number Tag) to check the history. Check how many occurrences happened over the last 3-6 months. Check if the issue was persistent and affecting several nodes or if a whole rack is affected with inlet temp being higher that normal, then this indicates a persisting environmental problems that to beesolve. Do not close the case as duplicate unless there is a clear action plan and conclusions to resolve the temperature issue. 

5. If the PE team does not find an issue or if the history contains many occurrences from the same alert (for 3 months or more) then consult with an L2 over Swarm and prepare to work order a CE to review the environmental conditions of the rack and nodes affected. 
 
Gen 2: 
 
1. Check the status of the temperature sensors using cs_hal.
Example:
# cs_hal sensors temp
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
System Board      Temperature         SSB Therm Trip    OK
System Board      Temperature         BB Inlet Temp     OK      32 Degrees Celsius
CPU (DCMI Compat) Temperature         HSBP Temp         OK      -222 Degrees Celsius
System Board      Temperature         SSB Temp          OK      60 Degrees Celsius
System Board      Temperature         BB BMC Temp       OK      51 Degrees Celsius
System Board      Temperature         P1 VR Temp        OK      38 Degrees Celsius
System Board      Temperature         IB Temp           OK      46 Degrees Celsius
System Board      Temperature         Exit Air Temp     OK      54 Degrees Celsius
Front Panel       Temperature         IOM Temp          OK      43 Degrees Celsius
Drive Backplane   Temperature         HSBP PSOC         OK      37 Degrees Celsius
Front Panel       Temperature         LAN NIC Temp      OK      67 Degrees Celsius
Power Supply      Temperature         PS1 Temperature   OK      34 Degrees Celsius
Power Supply      Temperature         PS2 Temperature   OK      34 Degrees Celsius
Processor         Temperature         P1 Therm Margin   OK      216 Degrees Celsius
Processor         Temperature         P2 Therm Margin   OK      206 Degrees Celsius
Processor         Temperature         P1 Therm Ctrl %   OK      0 Unspecified
Processor         Temperature         P2 Therm Ctrl %   OK      0 Unspecified
Processor         Temperature         P1 DTS Therm Mgn  OK      216 Degrees Celsius
Processor         Temperature         P2 DTS Therm Mgn  OK      206 Degrees Celsius
Processor         Temperature         P1 VRD Hot        OK
Processor         Temperature         P2 VRD Hot        OK
System Board      Temperature         DIMM Thrm Mrgn 1  OK      201 Degrees Celsius
System Board      Temperature         DIMM Thrm Mrgn 2  OK      200 Degrees Celsius
System Board      Temperature         DIMM Thrm Mrgn 3  OK      198 Degrees Celsius
System Board      Temperature         DIMM Thrm Mrgn 4  OK      197 Degrees Celsius
System Board      Temperature         Agg Thrm Mgn 1    OK      233 Degrees Celsius
2. Follow the same steps are Gen 3 (but do not report to PowerEdge), more details will be updated for Gen2 in the future. 