ECS:RAP015:溫度故障;症狀代碼:2010

Summary: 節點上的溫度感應器回報達到嚴重等級。

This article applies to This article does not apply to This article is not tied to any specific product. Not all product versions are identified in this article.

Symptoms

溫度感應器偵測到溫度高於臨界閾值。
可能元件未正確運作,導致溫度感應器回報已達到嚴重等級。
節點上的溫度感應器回報已達到嚴重等級。

Cause

發生導致溫度感應器超過嚴重等級的問題。

Resolution

若為 Gen2,請捲動至底部。

Gen3 硬體: 

1.在報告的節點上使用cs_hal檢查溫度感應器的狀態。

命令: 
#cs_hal sensors temp
 
範例:若為 Gen 3,則只有三個 Temp 感應器,如下所示。
 
admin@n1-mgmt:~>  cs_hal sensors temp
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      53 Degrees Celsius
Processor         Temperature         Temp              OK      54 Degrees Celsius
System Board      Temperature         Inlet Temp        CRIT    40 Degrees Celsius; above critical threshold
System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
admin@n1-mgmt:~>
2. 檢查機架中的所有節點,並查看 其他節點 是否回報溫度感應器 不是「OK」

命令: 
viprexec -i  cs_hal sensors temp

範例:在此範例中,機架上半部分的多個節點回報進氣溫度過高。 
admin@n1-mgmt:~> viprexec -i  cs_hal sensors temp

Output from host : 192.168.219.1
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      53 Degrees Celsius
Processor         Temperature         Temp              OK      53 Degrees Celsius
System Board      Temperature         Inlet Temp        CRIT    40 Degrees Celsius; above critical threshold
System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.2
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      47 Degrees Celsius
Processor         Temperature         Temp              OK      49 Degrees Celsius
System Board      Temperature         Inlet Temp        CRIT    39 Degrees Celsius; above critical threshold
System Board      Temperature         Exhaust Temp      OK      50 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.3
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      46 Degrees Celsius
Processor         Temperature         Temp              OK      46 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      35 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      47 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.4
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      48 Degrees Celsius
Processor         Temperature         Temp              OK      50 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      35 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      47 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.5
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      48 Degrees Celsius
Processor         Temperature         Temp              OK      50 Degrees Celsius
System Board      Temperature         Inlet Temp        WARN    38 Degrees Celsius; above non-critical threshold
System Board      Temperature         Exhaust Temp      OK      49 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.6
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      50 Degrees Celsius
Processor         Temperature         Temp              OK      52 Degrees Celsius
System Board      Temperature         Inlet Temp        CRIT    39 Degrees Celsius; above critical threshold
System Board      Temperature         Exhaust Temp      OK      51 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.7
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      45 Degrees Celsius
Processor         Temperature         Temp              OK      48 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      36 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      47 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.8
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      51 Degrees Celsius
Processor         Temperature         Temp              OK      49 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      31 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      43 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.9
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      52 Degrees Celsius
Processor         Temperature         Temp              OK      51 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      30 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      42 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.10
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      54 Degrees Celsius
Processor         Temperature         Temp              OK      51 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      28 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      41 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
 192.168.219.7
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      45 Degrees Celsius
Processor         Temperature         Temp              OK      48 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      36 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      47 Degrees Celsius

Output from host : 192.168.219.11
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      56 Degrees Celsius
Processor         Temperature         Temp              OK      55 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      27 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      40 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.12
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      59 Degrees Celsius
Processor         Temperature         Temp              OK      59 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      26 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      38 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.13
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      51 Degrees Celsius
Processor         Temperature         Temp              OK      49 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      26 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      36 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.14
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      57 Degrees Celsius
Processor         Temperature         Temp              OK      60 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      26 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      38 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.15
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      59 Degrees Celsius
Processor         Temperature         Temp              OK      59 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      26 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      39 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.

Output from host : 192.168.219.16
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
Processor         Temperature         Temp              OK      56 Degrees Celsius
Processor         Temperature         Temp              OK      56 Degrees Celsius
System Board      Temperature         Inlet Temp        OK      26 Degrees Celsius
System Board      Temperature         Exhaust Temp      OK      38 Degrees Celsius

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
admin@n1-mgmt:~>

3.可能的情況:
  1. 一個節點僅 報告一個或多個感應器:如果僅在溫度報告為「OK」的一個節點上出現問題,則很可能表示零件有問題,或節點因為內部問題而無法維持良好的氣流,而非機架問題。
  2. 多個節點 受到影響,這更多是機架本身或資料中心內部的環境問題


4.檢查風扇執行正常。如果沒有,則可能需要更換風扇。

命令:

#cs_hal sensors fan
範例: 
admin@ecs:~>cs_hal sensors fan

Output from host : 192.168.219.1
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
System Board      Fan                 Fan1              OK      12600 RPM
System Board      Fan                 Fan2              OK      12600 RPM
System Board      Fan                 Fan3              OK      16920 RPM
System Board      Fan                 Fan4              OK      16800 RPM
System Board      Fan                 Fan5              OK      17040 RPM
System Board      Fan                 Fan6              OK      16920 RPM
System Board      Fan                 Fan Redundancy    OK      fully redundant;

NOTE: on Axum and EX-series, use "sudo -i racadm getsensorinfo" to obtain sensor information.
3.如果所有風扇均回報正常,這表示風扇系統沒有問題。請聯絡 Power Edge 團隊 ,檢查零件是否需要更換。如果有風扇回報問題,請依照 ECS:Dial Home:風扇故障;症狀代碼:2008

年4.重要事項 :使用 https://central.dell.com/case-lookup/  並查閱 PSNT (產品序號標籤) 來檢查歷程記錄。查看過去 3-6 個月內發生的次數。檢查問題是否持續存在並影響到數個節點,或是整個機架受到進氣溫度高於正常溫度的影響,則表示需要專門解決的環境問題持續存在。除非有明確的行動計劃和結論來解決溫度問題,否則請勿將案例視為重複案例。

5.如果 PE 團隊找不到問題,或歷程記錄包含來自相同警示的多次事件 (持續 3 個月或更久),請諮詢 L2 over Swarm 準備工作訂單 CE ,以檢閱受影響機架和節點的環境條件。 
 
Gen 2: 
 
1.使用 cs_hal檢查溫度感應器的狀態。
範例:
# cs_hal sensors temp
Entity            Type                Label             Status  Info
-----             -----               -----             -----   -----
System Board      Temperature         SSB Therm Trip    OK
System Board      Temperature         BB Inlet Temp     OK      32 Degrees Celsius
CPU (DCMI Compat) Temperature         HSBP Temp         OK      -222 Degrees Celsius
System Board      Temperature         SSB Temp          OK      60 Degrees Celsius
System Board      Temperature         BB BMC Temp       OK      51 Degrees Celsius
System Board      Temperature         P1 VR Temp        OK      38 Degrees Celsius
System Board      Temperature         IB Temp           OK      46 Degrees Celsius
System Board      Temperature         Exit Air Temp     OK      54 Degrees Celsius
Front Panel       Temperature         IOM Temp          OK      43 Degrees Celsius
Drive Backplane   Temperature         HSBP PSOC         OK      37 Degrees Celsius
Front Panel       Temperature         LAN NIC Temp      OK      67 Degrees Celsius
Power Supply      Temperature         PS1 Temperature   OK      34 Degrees Celsius
Power Supply      Temperature         PS2 Temperature   OK      34 Degrees Celsius
Processor         Temperature         P1 Therm Margin   OK      216 Degrees Celsius
Processor         Temperature         P2 Therm Margin   OK      206 Degrees Celsius
Processor         Temperature         P1 Therm Ctrl %   OK      0 Unspecified
Processor         Temperature         P2 Therm Ctrl %   OK      0 Unspecified
Processor         Temperature         P1 DTS Therm Mgn  OK      216 Degrees Celsius
Processor         Temperature         P2 DTS Therm Mgn  OK      206 Degrees Celsius
Processor         Temperature         P1 VRD Hot        OK
Processor         Temperature         P2 VRD Hot        OK
System Board      Temperature         DIMM Thrm Mrgn 1  OK      201 Degrees Celsius
System Board      Temperature         DIMM Thrm Mrgn 2  OK      200 Degrees Celsius
System Board      Temperature         DIMM Thrm Mrgn 3  OK      198 Degrees Celsius
System Board      Temperature         DIMM Thrm Mrgn 4  OK      197 Degrees Celsius
System Board      Temperature         Agg Thrm Mgn 1    OK      233 Degrees Celsius
2.請依照與 Gen 3 相同的步驟 (但不會回報給 PowerEdge),更多詳細資料將於日後更新為 Gen 2。 