This product
is intended for restricted access locations (dedicated equipment rooms,
equipment closet, or the like) in accordance with the National Electrical
Code, American National Standards Institute (ANSI)/National Fire Protection
Association (NFPA) 70.
CAUTION: Wire the unit with copper
only. Unless otherwise specified, use only 4 American Wire Gauge (AWG)
wire rated minimum 90 ºC (194 ºF) for source and return. Protect the
–(48–60) V DC (1 wire) with a branch circuit overcurrent protection
rated 100 A for DC with a high interrupt current rating.
Connect
the equipment to a –48 V DC supply source that is electrically isolated
from the AC source (reliably grounded 48 V DC SELV source). Ensure
that the –48 V DC source is secured to earth (ground).
NOTE: A readily
accessible disconnect device that is suitably approved and rated must
be incorporated in the field wiring.
CAUTION: When
stranded wiring is required, use approved wiring termination, such
as closed-loop or spade-type with upturned lugs. These terminations
are the appropriate size for the wires and must be double crimped,
one on the conductor and one on the insulation.
CAUTION: When installing the unit, the ground connection must
always be made first and disconnected last to prevent an energy hazard.
CAUTION: Never defeat the ground conductor or operate
the equipment in the absence of a suitably installed ground conductor.
Contact the appropriate electrical inspection authority or an electrician
if you are uncertain that suitable grounding is available.