Dell PowerEdge R730 Owner's Manual

Installing a DC power supply unit

Prerequisites

NOTE: For equipment using –(48–60) V DC power supply units (PSUs), a qualified electrician must perform all connections to DC power and to safety grounds. Do not attempt connecting to DC power or installing grounds yourself. All electrical wiring must comply with applicable local or national codes and practices. Damage due to servicing that is not authorized by Dell is not covered by your warranty. Read and follow all safety instructions that came with the product.
  1. Follow the safety guidelines listed in the Safety instructions section.
  2. Follow the procedure listed in the Before working inside your system section.
  3. If installed, remove the PSU blank.
  4. Verify that both the PSUs are of the same type and have the same maximum output power.
    NOTE: The maximum output power (shown in watts) is listed on the PSU label.

Steps

  1. Slide the PSU into the chassis until the PSU is fully seated and the release latch snaps into place.
    NOTE: If you have unlatched the cable management arm, relatch it. For information about the cable management arm, see the rack documentation.
  2. Connect the safety ground wire.
  3. Install the DC power connector in the PSU.
    CAUTION: When connecting the power wires, ensure that you secure the wires with the strap to the PSU handle.
  4. Connect the wires to a DC power source.
    NOTE: When installing, hot-swapping, or hot-adding a new PSU, wait for 15 seconds for the system to recognize the PSU and determine its status. The PSU status indicator turns green to signify that the PSU is functioning properly.
    Figure 1. Installing a DC PSU
    This figure shows installing a DC PSU.
    1. release latch
    2. power supply status indicator
    3. PSU
    4. power connector
    5. PSU handle

Next steps

  • Follow the procedure listed in the After working inside your system section.