Dell PowerEdge C6300 enclosure supports up
to two AC or HVDC power supply units (PSUs). Dell PowerEdge C6320p
does not support a mixed installation of 1400 W and 1600 W PSUs. The
1400 W and 1600 W PSUs are hot swappable and support hot swap in any
condition if the system has the power throttling feature enabled.
Table 1. PSU specifications For 1400 W AC PSUs, the maximum heat dissipation
is 5220.763 BTU/hr, voltage is 200-240 V AC, and maximum input current
is 9 A. Initial inrush current cannot exceed 55 A and secondary inrush
current cannot exceed 25 A. For 1600 W AC and voltage of 100-120 V
AC, heat dissipation is 5966.586 BTU/hr and maximum input current
is 12 A. Initial inrush current and secondary inrush current cannot
exceed 35 A. For 1600 W AC and voltage of 200-240 V AC, heat dissipation
is 5966.586 BTU/hr and maximum input current is 10 A. For 1400 W HVDC,
voltage is 240 V DC, maximum input current is 9 A, and maximum heat
dissipation is 5220.763 BTU/hr. Initial inrush current cannot exceed
55 A and Secondary inrush current cannot exceed 25 A. For 1600 W HVDC,
voltage is 240 V DC, maximum input current is 9 A, and maximum heat
dissipation is 5966.586 BTU/hr. Initial inrush current cannot exceed
55 A and Secondary inrush current cannot exceed 25 A.
PSU
Heat dissipation (maximum)
Frequency
Voltage
Maximum input current
Maximum inrush current (peak)
1400 W AC
5220.763 BTU/hr
50/60 Hz
200-240 V AC
9 A
Initial
inrush current cannot exceed 55 A (peak).
Secondary
inrush current cannot exceed 25 A (peak).
1400 W HVDC (China only)
–
240 V DC
9 A
1600 W AC
5966.586 BTU/hr
50/60 Hz
100-120 V AC
200-240 V AC
12 A
10 A
Initial inrush current
and secondary inrush current cannot exceed 35 A (peak).
1600 W HVDC
–
240 V DC
10 A