Fehler beim PowerScale-Node mit Fehler: smsatReadLogExtCB: no matching pccb found
Summary: Beim PowerScale-Node tritt ein Fehler mit folgendem Fehler auf: smsatReadLogExtCB: no matching pccb found -- Status 0x41 Error 0x40 phy 5 lba 0x36ceff96 satNCQ 0x1 satOrgIOContext 0xfffffe8ef3da07a8 reqType 0x20001d00 sataTag 0x10 ...
This article applies to
This article does not apply to
This article is not tied to any specific product.
Not all product versions are identified in this article.
Symptoms
Node-Fehler mit dem folgenden Stack:
panic @ time 1728809334.451, thread 0xfffffe8ef3382b00: smsatReadLogExtCB: no matching pccb found -- status 0x41 error 0x40 phy 5 lba 0x36ceff96 satNCQ 0x1 satOrgIOContext 0xfffffe8ef3da07a8 reqType 0x20001d00 sataTag 0x10 time = 1728809334 cpuid = 2, TSC = 0x11360273d277825 Panic occurred in module pmspcv.ko loaded at 0xffffffff83de1000: Stack: -------------------------------------------------- pmspcv.ko:smsatReadLogExtCB+0x66d pmspcv.ko:smllSATACompleted+0xc9 pmspcv.ko:siIODone+0x152 pmspcv.ko:mpiSATACompletion+0x4c3 pmspcv.ko:mpiParseOBIomb+0x50e pmspcv.ko:siProcessOBMsg+0xb9 pmspcv.ko:saDelayedInterruptHandler+0x1cd pmspcv.ko:agtiapi_IntrHandlerx_+0x88 kernel:ithread_loop+0x21c kernel:fork_exit+0x82 -------------------------------------------------- Disabling swatchdog Dumping stacks (40960 bytes)
Cause
Ein seltenes bekanntes Problem, bei dem ein SATA-Laufwerk starke I/O-Anforderungen empfängt, verursacht diesen Fehler.
Resolution
Problemumgehung:
Legen Sie Folgendes fest sysctl:
isi_sysctl_cluster hw.iosched.max_disk_inprog_limit=16
Dauerhafte Lösung:
Führen Sie ein Upgrade auf eine der folgenden oder neueren Versionen durch:
- OneFS 9.4.0.16_GA RUP_2023-11
- OneFS 9.5.x
Affected Products
Isilon H500Article Properties
Article Number: 000236632
Article Type: Solution
Last Modified: 23 Oct 2024
Version: 1