Pular para o conteúdo principal
  • Faça pedidos de forma rápida e simples
  • Visualize os pedidos e acompanhe o status de envio
  • Crie e acesse uma lista dos seus produtos
  • Gerencie seus sites, produtos e contatos de nível de produto da Dell EMC usando o Company Administration.

Dell PowerEdge R730xd Owner's Manual

Expanded operating temperature

Table 1. Expanded operating temperature specificationsWhen the system is in continuous operation, the expanded operating temperature ranges from 5°C to 40°C at 5% to 85% RH with 29°C dew point. NOTE: Outside the standard operating temperature (10°C to 35°C), the system can operate continuously in temperatures as low as 5°C and as high as 40°C. For temperatures between 35°C and 40°C, de-rate maximum allowable temperature by 1°C per 175 m above 950 m (1°F per 319 ft). When the system is operating at < 1% of annual operating hours, the expanded operating temperature is –5°C to 45°C at 5% to 90% RH with 29°C dew point. NOTE: Outside the standard operating temperature (10°C to 35°C), the system can operate down to –5°C or up to 45°C for a maximum of 1% of its annual operating hours. For temperatures between 40°C and 45°C, de-rate maximum allowable temperature by 1°C per 125 m above 950 m (1°F per 228 ft).
Expanded operating temperature Specifications
Continuous operation 5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C to 35°C), the system can operate continuously in temperatures as low as 5°C and as high as 40°C.

For temperatures between 35°C and 40°C, de-rate maximum allowable temperature by 1°C per 175 m above 950 m (1°F per 319 ft).

≤ 1% of annual operating hours –5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C to 35°C), the system can operate down to –5°C or up to 45°C for a maximum of 1% of its annual operating hours.

For temperatures between 40°C and 45°C, de-rate maximum allowable temperature by 1°C per 125 m above 950 m (1°F per 228 ft).

NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported in the System Event Log.

Classifique este conteúdo

Preciso
Úteis
Fácil de entender
Este artigo foi útil?
0/3000 characters
  Forneça as classificações (de 1 a 5 estrelas).
  Forneça as classificações (de 1 a 5 estrelas).
  Forneça as classificações (de 1 a 5 estrelas).
  Selecione se o artigo foi útil ou não.
  Os comentários não podem conter estes caracteres especiais: <>()\