Gå til hovedindhold
  • Afgiv ordrer hurtigt og nemt
  • Se ordrer og spor status for din forsendelse
  • Opret og få adgang til en liste med dine produkter
  • Administrer dine Dell EMC-websteder, -produkter og -kontaktpersoner på produktniveau ved hjælp af Company Administration (Virksomhedsadministration).

Dell PowerEdge M630 Systems (VRTX Enclosure) Owner's Manual

Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous contamination. If the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Table 1. Particulate contamination specifications Air filtration specification: Data center air filtration as defined by ISO Class 8 per ISO 14644-1 should have a 95% upper confidence limit. Note: This condition applies only to data center environments. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor. Note: Air entering the data center must have MERV11 or MERV13 filtration. Conductive dust specification: Air must be free of conductive dust, zinc whiskers, or other conductive particles. Note: This condition applies to data center and nondata center environments. Corrosive dust specification: Air must be free of corrosive dust. Residual dust present in the air must have a deliquescent point less than 60% relative humidity. Note: This condition applies to data center and nondata center environments.

Particulate contamination

Specifications

Air filtration

Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
NOTE: This condition applies only to data center environments. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.
NOTE: Air entering the data center must have MERV11 or MERV13 filtration.

Conductive dust

Air must be free of conductive dust, zinc whiskers, or other conductive particles.
NOTE: This condition applies to data center and nondata center environments.

Corrosive dust

  • Air must be free of corrosive dust.
  • Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE: This condition applies to data center and nondata center environments.
Table 2. Gaseous contamination specifications The following table defines the limitations that help avoid any damages to the IT equipment and/or failure from gaseous contamination.

Gaseous contamination

Specifications

Copper coupon corrosion rate

<300 Å/month per Class G1 as defined by ANSI/ ISA71.04-1985.

Silver coupon corrosion rate

<200 Å/month as defined by AHSRAE TC9.9.

NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Bedøm indholdet

Nøjagtig
Nyttig
Nemt at forstå
Var denne artikel nyttig?
0/3000 characters
  Angiv vurderinger (1-5 stjerner).
  Angiv vurderinger (1-5 stjerner).
  Angiv vurderinger (1-5 stjerner).
  Angiv, om artiklen var nyttig eller ej.
  Kommentarer må ikke indeholde følgende specialtegn: <>()\