Prerequisites
Use Dell Storage Manager to send SupportAssist information to technical support.
Use Dell Storage Manager to edit the Storage Center settings and set the operation mode of the Storage Center to Maintenance mode.
Remove the Mezzanine Card:
Shut down the storage controller using Dell Storage Manager .
Make sure that all cables plugged into the storage controller are labeled.
Disconnect the cables from the storage controller that was shut down.
Remove the storage controller from the chassis.
CAUTION: To prevent a thermal shutdown of the storage system, the service baffle must be installed within three minutes of removing the storage controller.
Install the service baffle into the empty slot in the chassis.
Remove the cover of the storage controller.
Remove riser 1 from the storage controller.
Remove the screw that holds the blank slot cover or mezzanine card in place.
(Existing mezzanine card only) Press the release latch and lift the back end of the mezzanine card until it becomes free of the connector.
Remove the blank slot cover or mezzanine card from the storage controller.
Install the Mezzanine Card:
Angle the front of the mezzanine card into the slot on the front of the storage controller.
Mezzanine card
Screw
Touchpoint (blue dot)
Connector
Release latch
Press down simultaneously on the release latch and the blue dot on the rear of the mezzanine card until the card is secure in the connector.
Insert and tighten the screw that secures the mezzanine card to the storage controller.
Replace riser 1 in the storage controller.
Replace the cover on the storage controller.
Remove the service baffle from the chassis.
CAUTION: To prevent a thermal shutdown of the storage system, the storage controller must be installed within three minutes of removing the service baffle.
Install the storage controller in the chassis.
Reconnect the cables to the storage controller.
Clear the storage controller swap status from the Hardware tab in Dell Storage Manager.
Use Dell Storage Manager to edit the Storage Center settings and set the operation mode of the Storage Center to Production mode.
If you added a mezzanine card to an empty mezzanine card slot, use Dell Storage Manager to configure the new fault domains.
Use Dell Storage Manager to send SupportAssist information to technical support.