CAUTION: Many
repairs may only be done by a certified service technician. You should
only perform troubleshooting and simple repairs as authorized in your
product documentation, or as directed by the online or telephone service
and support team. Damage due to servicing that is not authorized by
Dell is not covered by your warranty. Read and follow the safety instructions
that came with the product.
NOTE: This
is a Field Replaceable Unit (FRU). Removal and installation procedures
should be performed only by Dell certified service technicians.
NOTE: You must remove the
system board to replace a faulty system board.
Follow the safety guidelines listed in the Safety
instructions section.
Follow the procedure listed in the Before working
inside your system section.
Remove the system board.
Unpack the new system board assembly.
Keep the Phillips #2 screwdriver, the 4 mm and 5 mm
Hex nut drivers ready.
CAUTION: Do not lift the system board by holding a memory module, processor,
or other components.
CAUTION: Take care not to damage the system identification button while placing
the system board into the chassis.
Steps
Align the system board with the standoffs on
the chassis.
Secure the system board to the chassis with
the screws.
Next steps
Install the Trusted Platform Module (TPM). For information
about how to install TPM, see the Installing the trusted platform
modules section. For information about TPM, see the Trusted Platform
Module section.
Install the following components:
LOM riser card
PCIe mezzanine card
SSD cage
SSD backplane
SSD carriers
NOTE: Ensure that you reinstall
the SSD carriers into their original bays.
Cooling shroud
Memory modules
Processor(s) and heat sink(s)
Follow the procedure listed in the
After working inside your system section.
NOTE: If you are not installing
the sled in the enclosure, install the I/O connector cover.
Import your new or existing iDRAC
Enterprise license. See the iDRAC8 User's Guide at Dell.com/idracmanuals.
Ensure that you:
Use the Easy Restore feature to restore the Service
Tag. For more information, see the Restoring the Service Tag using
Easy Restore section.
If the Service Tag is not backed up in the backup
flash device, enter the system Service Tag manually. For more information,
see the Entering the system Service Tag section.
Update the BIOS and iDRAC versions.
Re-enable the Trusted Platform Module (TPM). For
more information, see the Re-enabling the TPM for BitLocker users
or Re-enabling the TPM for Intel TXT users section.