NOTE:For additional information
about environmental measurements for specific system configurations,
see Dell.com/environmental_datasheets.
Table 1. Temperature
specifications When the system is in continuous operation (for
altitude less than 950 m or 3117 ft), the temperature specification
ranges from 10°C to 35°C (50°F to 95°F) with no direct sunlight on
the equipment. When the system is not in operation, the temperature
specification is –40°C to 65°C (–40°F to 149°F). The Maximum temperature
gradient for both opertaion and non-opertaional systems is 20°C/h
(36°F/h). Information about fresh air specification is described in
the Expanded Operating Temperature section.
Temperature
Specifications
Storage
–40°C to 65°C (–40°F to 149°F)
Continuous operation (for altitude less than 950
m or 3117 ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight
on the equipment
Maximum temperature gradient (operating and storage)
20°C/h (36°F/h)
Table 2. Relative humidity
specificationsFor a non-operational system, the ambient relative
humidity ranges from 5% to 95% with 33°C (91°F) maximum dew point.
Atmosphere must be non-condensing at all times. For an operational
system, the ambient relative humidity ranges from 10% to 80% with
29°C (84.2°F) maximum dew point.
Relative humidity
Specifications
Storage
5% to 95% RH with 33°C (91°F) maximum dew point.
Atmosphere must be non-condensing at all times.
Operating
10% to 80% RH with 29°C (84.2°F) maximum dew point.
Table 3. Maximum vibration
specificationsThe maximum vibration specification of an operational
system is 0.26 Grms at 5 Hz to 350 Hz (all operation orientations).The
maximum vibration specification of a non-operational system is 1.87
Grms at 10 Hz to 500 Hz for 15 min (all six sides tested).
Maximum vibration
Specifications
Operating
0.26 Grms at 5 Hz to 350 Hz (all operation
orientations)
Storage
1.87 Grms at 10 Hz to 500 Hz for 15
minutes (all six sides tested)
Table 4. Maximum shock
pulse specificationsThe maximum shock specification of an operational
system is one shock pulse in the positive z axes of 31 G for 2.6 ms
in all operational orientations. The maximum shock specification of
a non-operational system is six consecutively executed shock pulses
in the positive and negative x, y, and z axes (one pulse on each side
of the system) of 71 G for up to 2 ms.
Maximum shock pulse
Specifications
Operating
One shock pulse in the positive z axes of 31 G
for 2.6 ms in all operational orientations.
Storage
Six consecutively executed shock pulses in the
positive and negative x, y, and z axes (one pulse on each side of
the system) of 71 G for up to 2 ms.
Table 5. Maximum altitude
specificationsThe maximum altitude specification for an operational
system is 3048 m (10,000 ft). The maximum altitude specification for
a non-operational system is 12,000 m (39,370 ft).
Maximum altitude
Specifications
Operating
3048 m (10,000 ft)
Storage
12,000 m (39,370 ft)
Table 6. Operating temperature
de-rating specificationIf the operating temperature of a system is up to
35 °C (95 °F), the maximum temperature is reduced by 1°C/300 m (1°F/547
ft) above 950 m (3,117 ft).
Operating temperature de-rating
Specifications
Up to 35°C (95°F)
Maximum temperature is reduced by 1°C/300 m (1°F/547
ft) above 950 m (3,117 ft)