Hardware acclimation times

Units must acclimate to the operating environment before applying power. This requires the unpackaged system or component to reside in the operating environment for up to 16 hours in order to thermally stabilize and prevent condensation.

Transit/storage environment Operating environment temperature Acclimation time
Temperature Humidity
Nominal

68-72°F (20-22°C)

Nominal

40-55% RH

Nominal 68-72°F (20-22°C)

40-55% RH

0-1 hour
Cold

<68°F (20°C)

Dry

<30% RH

<86°F (30°C) 4 hours
Cold

<68°F (20°C)

Damp

≥30% RH

<86°F (30°C) 4 hours
Hot

>72°F (22°C)

Dry

<30% RH

<86°F (30°C) 4 hours
Hot

>72°F (22°C)

Humid 30-45% RH <86°F (30°C) 4 hours
Humid 45-60% RH <86°F (30°C) 8 hours
Humid ≥60% RH <86°F (30°C) 16 hours
Unknown <86°F (30°C) 16 hours
  • If there are signs of condensation after the recommended acclimation time has passed, allow an additional eight (8) hours to stabilize.
  • Systems and components must not experience changes in temperature and humidity that are likely to cause condensation to form on or in that system or component. Do not exceed the shipping and storage temperature gradient of 45°F/hr (25°C/hr).