Dell PowerEdge R660 Installation and Service Manual

Installing a cooling fan module

Prerequisites

  1. Follow the safety guidelines listed in the Safety instructions.
  2. Follow the procedure listed in Before working inside your system.
  3. If installed, remove the air shroud.

Steps

  1. Align and place the fan module connector horizontally with the connector on the system board.
    NOTE:The procedure to remove standard (STD) or high performance gold (HPR Gold) dual cooling fan modules are same.
  2. Press the orange touch point on the cooling fan module until firmly connected.
    Figure 1. Installing a cooling fan module
    This image shows how to install a cooling fan module.

Next steps

  1. If applicable, replace the air shroud.
  2. Follow the procedure listed in After working inside your system.